 RMH Module  • 116 •  Chapter 6 Features
Process Value Function
The Process Value (PV) function block accepts multiple in-
puts and performs a programmed math function to derive 
an output value with Filter and Offset values applied. It 
is assumed that no input error conditions apply. Some PV 
operations must be performed in the user's units. Func-
tions may combine multiple inputs. Those inputs may have 
incompatible units from a logical point of view. As a result, 
unless otherwise indicated, the presentation of the output 
value is the same as Source A. This accommodates tem-
peratures being multiplied, divided and offset by constants 
and process inputs. Only inputs that have a source associ-
ated to them are used in the calculations.
An error, when read, can indicate any of the following: 
None, Open, Shorted, Measurement Error, Bad Cal Data, 
Ambient Error, RTD Error, Fail, Math Error, Not Sourced, 
Stale
Source  AValue 
Source  BValue 
Source  CValue 
Source  DValue 
Source  EValue 
Process Value 
Overview
Instances - 16 per RMH
Source Function A
Source Instance A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Source Function C
Source Instance C
Source Zone C
Source Error C
Source Function D
Source Instance D
Source Zone D
Source Error D
Source Function E
Source Instance E
Source Zone E
Source Error E
Pressure Units
Altitude Units
Barometric Pressure
Cross Over Point
Cross Over Band
Function
Filter 
Offset
Output Value
Ranges specified in units or  F
if expressed in  C, range is smaller.
∞
∞
Error
[SFn;A] Source Function A : Analog Input, Process Value
[SFn;C] Source Function C : None, Analog Input, Linearization, Math, Process Value, 
Variable
[SFn;E] Source Function E : None, Alarm, Compare, Counter, Digital I/O, Profile 
Event Out A to H, Function Key, Logic, Timer, Variable
[SFn;b] Source Function B : 
Variable
None, Analog Input, Linearization, Math, Process Value, 
[SFn;d] Source Function D : None, Analog Input, Linearization, Math, Process Value, 
Variable
[S2;A] Source  A : 0 to 16Zone 
[S2;C] Source  C : 0 to 16Zone 
[S2;E] Source  E : 0 to 16Zone 
[S2;b] Source  B : 0 to 16Zone 
[S2;d] Source  D : 0 to 16Zone 
[Si;A] Source  A : 1 to 250Instance 
[Si;C] Source  C : 1 to 250Instance 
[Si;b] Source  B : 1 to 250Instance 
[S;id] Source  D : 1 to 250Instance 
[Fn] Function : Off, Sensor Backup, Average, Crossover, Wet Bulb/Dry Bulb, Switch 
Over, Differential, Ratio, Add, Multiply, Absolute Difference, Minimum, Maximum, 
Square Root, Vaisala RH Compensation, Pressure to Altitude
[C;P] Cross Over Point : -1,999.000 to 9,999.000
[C;b] Cross Over Band : -1,999.000 to 9,999.000
[oFSt] Offset : -1,999.000 to 9,999.000
[P;unt] Pressure Units : PSI, Torr, mBar, Atmosphere, Pascal
[A;unt] Altitude Units : Feet, Kilofeet
[b;Pr] Barometric Pressure : 10.0 to 16.0
[FiL] Filter : 0.0 to 60.0 seconds
[``Pu]
[oPEr]
 Process Value Menu
 Operation Page
[Si;E] Source  E : 1 to 250Instance 
[``Pu]
[`SEt]
 Process Value Menu
 Setup Page
[Su;A] Source  A : -1,999.000 to 9,999.000Value 
[Su;b] Source Value B : -1,999.000 to 9,999.000
[Su;C] Source Value C : -1,999.000 to 9,999.000
[Su;d] Source Value D : -1,999.000 to 9,999.000
[Su;E] Source Value E : Off, On
[o;u] Output Value : -1,999.000 to 9,999.000