User Manual
Watlow EZ-ZONE
®
RME Module • 75 • Chapter 4 Setup Page
RME Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[`o;S2]
[ o.S2]
Special Output (1 to 8)
Output 2 Size
If Function is set to Se-
quencer:
• Set the size of outputs 2
through 4 to represent
a percentage of the
total output capacity.
Outputs 2 through 4
will control using the
ON-OFF algorithm.
0 to 9,999 0 6676
[offset 80]
0x87 (135)
1 to 4
0x1D (29)
- - - - 35029 float
RWES
[`o;S3]
[ o.S3]
Special Output (1 to 8)
Output 3 Size
If Function is set to Se-
quencer:
• Set the size of outputs 2
through 4 to represent
a percentage of the
total output capacity.
Outputs 2 through 4
will control using the
ON-OFF algorithm.
0 to 9,999 0 6678
[offset 80]
0x87 (135)
1 to 4
0x1E (30)
- - - - 35030 float
RWES
[`o;S4]
[ o.S4]
Special Output (1 to 8)
Output 4 Size
If Function is set to Se-
quencer:
• Set the size of outputs 2
through 4 to represent
a percentage of the
total output capacity.
Outputs 2 through 4
will control using the
ON-OFF algorithm.
0 to 9,999 0 6680
[offset 80]
0x87 (135)
1 to 4
0x1F (31)
- - - - 35031 float
RWES
[`t;dL]
[ t.dL]
Special Output (1 to 8)
Time Delay
If Function is set to Se-
quencer:
• Set in seconds to repre-
sent the minimum span
of time that must elapse
between the turn on of
one (on-off) output to
the next.
0 to 9,999 seconds 0 6670
[offset 80]
0x87 (135)
1 to 4
0x1A (26)
- - - - 35026 uint
RWES
[`ot;o]
[ ot.o]
Special Output (1 to 8)
Output Order
If Function is set to Se-
quencer:
• Set to Linear to turn
the on-off outputs on in
the same order every
time. Select Progres-
sive to rotate the order
to balance usage and
wear on contactors and
heaters.
[`Lin] Linear (1509)
[`Pro] Progressive (1510)
Linear 6672
[offset 80]
0x87 (135)
1 to 4
0x1B (27)
- - - - 35027 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set