User Manual

Watlow EZ-ZONE
®
RME Module 74 Chapter 4 Setup Page
RME Module Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[`on;t]
[ on.t]
Special Output (1 to 4)
On Time
If Function is set to Com-
pressor Control:
Set Minimum On Time
and Minimum Off Time
to the minimum span
of time, in seconds, that
the compressor will be
on or off.
0 to 9,999 seconds 20 6662
[offset 80]
0x87 (135)
1 to 4
0x16 (22)
190 35022 uint
RWES
[`oF;t]
[ oF.t]
Special Output (1 to 4)
Off Time
0 to 9,999 seconds 20 6664
[offset 80]
0x87 (135)
1 to 4
0x17 (23)
191 35023 uint
RWES
[`t;t]
[ t.t]
Special Output (1 to 8)
Valve Travel Time
If Function is set to Motor-
ized Valve:
Source A will determine
the valve position.
Set this time in seconds
representing the time
that it will take the
valve to travel between
fully closed and fully
open.
10 to 9,999 seconds 120 6666
[offset 80]
0x87 (135)
1 to 4
0x18 (24)
192 35024 uint
RWES
[``db]
[ db]
Special Output (1 to 4)
Dead Band
If Function is set to Motor-
ized Valve:
Set to the minimum
valve adjustment as a
percentage, represent-
ing the movement of the
valve in a single action.
A small value improves
accuracy and depletes
valve life where a large
value reduces the num-
ber of adjustments (less
accurate)and the wear
on the mechanism.
1.0 to 100.0% 2 6668
[offset 80]
0x87 (135)
1 to 4
0x19 (25)
193 35025 float
RWES
[`o;S1]
[ o.S1]
Special Output (1 to 4)
Output 1 Size
If Function is set to Se-
quencer:
Set Output 1 Size, as a
percentage of the total
capacity of all output
devices, or vernier out-
put. This value must
be larger than the
values set for outputs 2
through 4.
0 to 9,999 10 6674
[offset 80]
0x87 (135)
1 to 4
0x1C (28)
- - - - 35028 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set