User Manual

Watlow EZ-ZONE
®
RME Module 73 Chapter 4 Setup Page
RME Module Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[sfn;B]
[SFn.B]
Special Output (1 to 4)
Source Function B
Set the type of function
that will be used for this
source.
[nonE] None (61)
[`C;Pr] Cool Power, Control
Loop (161)
[`h;Pr] Heat Power, Control
Loop (160)
[PWr] Power, Control Loop
(73)
[`Lnr] Linearization (238)
[MAt] Math (240)
[`uAr] Variable (245)
None 6622
[offset 80]
0x87 (135)
1 to 4
2
184 35002 uint
RWES
[`si;B]
[ Si.B]
Special Output (1 to 4)
Source Instance B
Set the instance of the
function selected above.
1 to 250 1 6626
[offset 80]
0x87 (135)
1 to 4
4
185 35004 uint
RWES
[`s2;B]
[ SZ.B]
Special Output (1 to 4)
Source Zone B
Set the zone of the function
selected above.
0 to 16 0 6630
[offset 80]
0x87 (135)
1 to 4
6
- - - - 35006 uint
RWES
[Pon;A]
[Pon.A]
Special Output (1 to 4)
Power On Level 1
If Function is set to Com-
pressor Control:
Use Source A for a first
loop to inform the function
whether the compressor
will soon be required.
Set Power On Level 1
and Power Off Level 1
to the Source A values
that will switch the
compressor on and off.
-100.00 to 100.00% 0 6654
[offset 80]
0x87 (135)
1 to 4
0x12 (18)
186 35018 float
RWES
[PoF;A]
[PoF.A]
Special Output (1 to 4)
Power Off Level 1
-100.00 to 100.00% 5 6656
[offset 80]
0x87 (135)
1 to 4
0x13 (19)
187 35019 float
RWES
[Pon;b]
[Pon.b]
Special Output (1 to 4)
Power On Level 2
If Function is set to Com-
pressor Control:
Use Source B for a second
loop to inform the function
whether the compressor
will soon be required.
Set Power On Level 2
and Power Off Level 2 to
the Source B values that
will switch the compres-
sor on and off.
-100.00 to 100.00% 0 6658
[offset 80]
0x87 (135)
1 to 4
0x14 (20)
188 35020 float
RWES
[PoF;b]
[PoF.b]
Special Output (1 to 4)
Power Off Level 2
-100.00 to 100.00% 5 6660
[offset 80]
0x87 (135)
1 to 4
0x15 (21)
189 35021 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set