User Manual
Watlow EZ-ZONE
®
RME Module • 50 • Chapter 4 Setup Page
RME Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[`C;SC]
[ C.SC]
Current (1 to 4)
Scaling
Use Input Current Scaling
to adjust scaling to match
the transformer's high
range, in amperes.
0 to 9,999.000 50.0 1122
[offset 50]
0x73 (115)
1 to 4
0x16 (22)
148 15022 float
RWES
[C;;oFs]
[C.oFS]
Current (1 to 4)
Heater Offset
Heater Current Offset is
used to calibrate the cur-
rent reading with an offset
value.
-9,999.000 to 9,999.000 0.0 1100
[offset 50]
0x73 (115)
1 to 4
0xB (11)
149 15011 float
RWES
[`C;;Si]
[ C.Si]
Current (1 to 4)
Output Source Instance
With Current Output
Source Instance, set the
output on which the cur-
rent will be monitored.
1 to 250 1 1116
[offset 50]
0x73 (115)
1 to 4
0x13 (19)
150 15019 uint
RWES
[``S2]
[ SZ]
Current (1 to 4)
Source Zone
Set the zone of the function
selected above.
0 to 16 0 - - - - - - - - - - - - 15036 uint
RWES
[`Lnr]
[`Set]
Linearization Menu
[``Fn]
[ Fn]
Linearization (1 to 8)
Function
Set how this function will
linearize Source A.
[`oFF] Off (62)
[intr] Interpolated (1482)
[Stpd] Stepped (1483)
Off 5548
[offset 70]
0x86 (134)
1 to 8
5
155 34005 uint
RWES
[`s2;A]
[ SZ.A]
Linearization (1 to 16)
Source Zone A
Set the zone of the function
selected above.
0 or 16 0 5544
[offset 70]
0x86 (134)
1 to 8
3
- - - - 34003 uint
RWES
[Unit]
[Unit]
Linearization (1 to 8)
Units
Set the units of Source A.
[`Src] Source (1539)
[nonE] None (61)
[`A;tP] Absolute Tempera-
ture (1540)
[`r;tp] Relative Tempera-
ture (1541)
[PWr] Power (73)
[`pro] Process (75)
[``rh] Relative Humidty
(1538)
Source 5596
[offset 70]
0x86 (134)
1 to 8
0x1D (29)
- - - - 34029 uint
RWES
[`iP;1]
[ ip.1]
Linearization (1 to 8)
Input Point 1
Set the value that will be
mapped to output 1.
-1,999.000 to 9,999.000 0.0 5554
[offset 70]
0x86 (134)
1 to 8
8
157 34008 float
RWES
[`oP;1]
[ op.1]
Linearization (1 to 8)
Output Point 1
Set the value that will be
mapped to input 1.
-1,999.000 to 9,999.000 0.0 5574
[offset 70]
0x86 (134)
1 to 8
0x12 (18)
158 34018 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set