Instruction Manual
Watlow EZ-ZONE
®
 RMC Module  • 160 •  Chapter 7 Features
Proportional (P) Control
Some processes need to maintain a temperature or 
process value closer to the set point than on-off con-
trol can provide. Proportional control provides closer 
control by adjusting the output when the temperature 
or process value is within a proportional band. When 
the value is in the band, the controller adjusts the 
output based on how close the process value is to the 
set point. 
The closer the process value is to the set point, the 
lower the output power. This is similar to backing 
off on the gas pedal of a car as you approach a stop 
sign. It keeps the temperature or process value from 
swinging as widely as it would with simple on-off 
control. However, when the system settles down, the 
temperature or process value tends to “droop” short 
of the set point.
With proportional control the output power level 
equals (set point minus process value) divided by the 
proportional band value.
In an application with one output assigned to 
heating and another assigned to cooling, each will 
have a separate proportional parameter. The heating 
parameter takes effect when the process temperature 
is lower than the set point, and the cooling param-
eter takes effect when the process temperature is 
higher than the set point.
Adjust the proportional band with Heat Pro-
portional Band [`h;Pb] or Cool Proportional Band 
[`C;Pb] (Operations Page, Loop Menu).
Time
Temperature
Proportional Control
Set Point
Proportional Band
Droop
Overshoot
Proportional plus Integral (PI) Control
The droop caused by proportional control can be cor-
rected by adding integral (reset) control. When the 
system settles down, the integral value is tuned 
to bring the temperature or process value closer to 
the set point. Integral determines the speed of the 
correction, but this may increase the overshoot at 
startup or when the set point is changed. Too much 
integral action will make the system unstable. Adjust 
the integral with Time Integral [``ti] (Operations 
Page, Loop Menu).
Proportional, Integral and Derivative (PID) Control
Use derivative (rate) control to minimize the over-
shoot in a PI-controlled system. Derivative (rate) ad-
justs the output based on the rate of change in the 
temperature or process value. Too much derivative 
(rate) will make the system sluggish.
Adjust the derivative with Time Derivative 
[``td] (Operations Page, Loop Menu).
Time
Temperature
PID Control
Set Point
Reduced Overshoot
Proportional Band
Proportional Band x 2
Heating Slows
Dead Band
In a PID application the dead bands above and below 
the set point can save an application’s energy and 
wear by maintaining process temperature within ac-
ceptable ranges. Use Dead Band to set an offset for 
the proportional band. With a negative value both 
the heating and cooling outputs are active when the 
process value is near the set point. A positive value 
prevents heating and cooling outputs from being on 
at the same time.
Proportional action ceases when the process value 
is within the dead band. Integral action continues to 
bring the process temperature to the set point.
Time 
Temperature 
Positive Dead Band 
Set Point 
Heat Output Active 
Cool Output Active 
When the dead band value is zero, the heat-
ing output activates when the temperature drops be-
low the set point, and the cooling output switches on 
when the temperature exceeds the set point.
Time 
Temperature 
Zero Dead Band 
Set Point 
Heat Output Active 
Cool Output Active 










