Instruction Manual

Watlow EZ-ZONE
®
RMC Module 109 Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[SFn;E]
[SFn.E]
Math (1 to 8)
Source Function E
Set the type of function
that will be used for this
source.
[none] None (61)
[ALM] Alarm (6)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[Ent;A] Profile Event Out A
(233)
[Ent;b] Profile Event Out B
(234)
[Ent;C] Profile Event Out C
(235)
[Ent;d] Profile Event Out D
(236)
[Ent;E] Profile Event Out E
(247)
[Ent;F] Profile Event Out F
(248)
[Ent;g] Profile Event Out G
(249)
[Ent;h] Profile Event Out H
(250)
[`FUn] Function Key (1001)
[`lgC] Logic (239)
[tMr] Timer (244)
[`uAr] Variable (245))
None 2848
[offset 70]
0x7D
(125)
1 to 8
5
- - - - 25005 uint
RWES
[`Si;E]
[ Si.E]
Math (1 to 8)
Source Instance E
Set the instance of the
function selected above.
1 to 250 1 2858
[offset 70]
0x7D
(125)
1 to 8
0xA (10)
- - - - 25010 uint
RWES
[`s2;E]
[ SZ.E]
Math (1 to 8)
Source Zone E
Set the zone of the func-
tion selected above.
0 to 16 0 2868
[offset 70]
0x7D
(125)
1 to 8
0xF (15)
- - - - 25015 uint
RWES
[`S;Lo]
[ S.Lo]
Math (1 to 8)
Scale Low
If Math function is set to
Process Scale, this will
scale Source A low value
to Range Low setting.
-1,999.000 to 9,999.000 0.0 2886
[offset 70]
0x7D
(125)
1 to 8
0x18 (24)
129 25024 float
RWES
[`S;hi]
[ S.hi]
Math (1 to 8)
Scale High
If Math function is set
to Process Scale, this
will scale Source A high
value to Range High
setting.
-1,999.000 to 9,999.000 1.0 2888
[offset 70]
0x7D
(125)
1 to 8
0x19 (25)
130 25025 float
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set