Owner manual
Watlow EZ-ZONE
®
 RMS Module  • 98 •  Chapter 6 Features
Process Value
Wet Bulb/Dry Bulb
Process Value
Switch Over
Process Value
Ratio
 Output Value = 
If display units of Source A = Source B, no display 
units on output value, else follow Source A
Filter [(A / B) + Offset]
Source Function A
Source Instance A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Source Function C
Source Instance C
Source Zone C
Source Error C
Source Function D
Source Instance D
Source Zone D
Source Error D
Source Function E
Source Instance E
Source Zone E
Source Error E
Source Function A
Source Instance A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Source Function C
Source Instance C
Source Zone C
Source Error C
Source Function D
Source Instance D
Source Zone D
Source Error D
Source Function E
Source Instance E
Source Zone E
Source Error E
Source Function A
Source Instance A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Source Function C
Source Instance C
Source Zone C
Source Error C
Source Function D
Source Instance D
Source Zone D
Source Error D
Source Function E
Source Instance E
Source Zone E
Source Error E
Source  AValue 
Source  BValue 
Source  CValue 
Source  DValue 
Source  EValue 
Output Value
Error
Source  AValue 
Source  BValue 
Source  CValue 
Source  DValue 
Source  EValue 
Output Value
Error
Source  AValue 
Source  BValue 
Source  CValue 
Source  DValue 
Source  EValue 
Output Value
Error
Process Value
Differential
Source Function A
Source Instance A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Source Function C
Source Instance C
Source Zone C
Source Error C
Source Function D
Source Instance D
Source Zone D
Source Error D
Source Function E
Source Instance E
Source Zone E
Source Error E
Source  AValue 
Source  BValue 
Source  CValue 
Source  DValue 
Source  EValue 
Output Value
Error
Pressure Units
Altitude Units
Barometric Pressure
Cross Over Point
Cross Over Band
Function
Filter 
Offset
Pressure Units
Pressure Units
Pressure Units
Altitude Units
Altitude Units
Altitude Units
Barometric Pressure
Barometric Pressure
Barometric Pressure
Cross Over Point
Cross Over Point
Cross Over Point
Cross Over Band
Cross Over Band
Cross Over Band
Function
Function
Function
Filter 
Filter 
Filter 
Offset
Offset
Offset
Output Value = Filter [(A - B) + Offset]
Display units follows Source A plus relative 
Source B
If E = OFF,   Filter [A + Offset]
If E = ON, Output Value = Filter [B + Offset]
Display units follows active source.
 Output Value =Output Value = Filter [Calculated Humidity + Offset] where
Source A is the Dry Bulb and Source B is the Wet Bulb
Note: Wet/Dry bulb temperatures are in degrees F and pressures are in 
PSI. Output Value is % relative humidity. Useful temperature range is 
10 to 350F