60 8LS User’s Guide
Setup 
Heat/Cool PB
Use this menu to set the Proportional Band.
Heat/Cool TI
Use this menu to set the Integral Term.
Selectable range:
 0-5000 seconds.
Heat/Cool TD
Use this menu to set the Derivative constant.
Selectable range:
 0-255 seconds.
Heat/Cool Output Filter
Use This menu to dampen the heat or cool output’s response. The output
responds to a step change by going to approximately 2/3 of its final
value within the number of scans you set here.
Selectable range:
 0-255.