The standard specifications listed in the 
Introduction
 section of this
manual apply to the 8LS-CP with the following additions:
Analog Inputs
Each CP Input:
• 
1 Loop Selectable Type N, K, R, or S T/C Reference Temperature for 
CP
• 
1 Loop Selectable % Carbon Potential (CP), Dew point (DP), or DC 
MV
• 
Carbon probe input
Carbon Probe Input Range:
• 
mV Range: 960 to 1275 mVdc
• 
CP Range: .10 to 1.40% Carbon
• 
Adjustable CO+CO2 Range: 1-30%
• 
DP Range: -40 to 300
º
 F/C
• 
Adjustable Hydrogen Range: 1-100%
Control Capability
CP PID Control
T/C Loop has standard PID control. 
Carbon Probe Loop PID control is reference to T/C Loop: output is
available for control when T/C Loop is between 1400 to 2400
º
F.
CP Trim Gas
A separate output is available for each CP input.
Selectable Digital Output 1-30 will be On when T/C Loop PV is
between 1400 to 2400
º
F and Off when PV is outside those limits.
Carbon Burn Off
Selectable Digital Output 1-30 with adjustable interval timer or contact
start and burn off period timer. A separate output is available for each
CP input.
• 
Interval timer range: 1 to 255 hours.
• 
Contact Start: Selectable Digital Input 1-12.
• 
Burn Off Period range: 1-45 minutes.
• 
Maximum Allowable Temperature: 1900 or 2100
º
F