Appendix A: Ramp Soak 
Copying the Setup from Another Profile
Use this menu to setup similar profiles quickly, by copying a profile to
another one.
Selectable Values:
 A to H.
Editing the Tolerance Alarm Time
Use this menu to set a tolerance time that applies to the entire profile.
When the segment goes out of tolerance,
• 
The segment goes into tolerance hold.
• 
The segment timer holds.
• 
The loop’s single loop display shows TOHO (Tolerance Hold).
When the segment has been out of tolerance for more than the tolerance
alarm time,
• 
The controller goes into tolerance alarm.
• 
The tolerance timer resets.
You must acknowledge the tolerance alarm by pressing the ALARM
ACK key before you can do any other editing.
Selectable Values: 
0:00 to 99:59 (minutes or hours, depending on the
time base setting).
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT
STATUS
OUTPUT%
 R/S PRO
 COPY? H
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT
STATUS
OUTPUT%
 A OUTTOL
 T? 1:00