User`s manual
7.2 WATLOW Series 982 User’s Manual
Programming, Chapter 7
Program Menu
[StYP]
Step Type: Choose from five different step types. When selecting Step
1, you will not see the jump-loop (JL) or link file (LFiL) step type.
Range: StPt, SoAh, JL, LFiL or End
Default: End
[StPt]
Set Point Step (StPt) : The following parameters are associated
with the set point step.
[``SP]
Set Point: The temperature the system tries to achieve for this step. This
is done linearly, producing a ramp from a beginning set point to this end
set point.
Range: rL1 to rH1
Default: 75°F/24°C or rL value if rL≥75°F/24°C or if rH≤75°F/24°C
[Hour]
Hour: The number of hours, plus the Min and SEC parameters equal the
total step time to achieve the temperature under the StPt step type.
Range: 0 to 99
Default: 0
Hidden if: PtYP = rAtE
[Min]
Minutes: The number of minutes plus the Hour and SEC parameters
equal the total step time to achieve the temperature under the StPt step
type.
Range: 0 to 59
Default: 0
Hidden if: PtYP = rAtE
[`SEC]
Seconds: The number of seconds plus the Hour and Min parameters
equal the total step time to achieve the temperature under the StPt step
type.
Range: 0 to 59
Default: 0
Hidden if: PtYP = rAtE
[rAte]
Rate: Represents the rate at which the set point changes in degrees per
minute. Decimal point location dependent on dEC1 (decimal 1) prompt.
Range: 0.0 to 360.0°F/0.0 to 200.0°C or 0.0 to 360.0 units
Default: 0.0
Hidden if: PtYP = ti
[Ent3]
Event 3: Selects whether Event 3 is on or off.
Range: On or OFF
Default: OFF
Hidden if: Hardware not present or Ot3 = AL3, AL3n or no
NOTE:
Decimal points may
not always be in the
position specified
depending on the
value of Decimal 1
in the Input Menu.