4.34 WATLOW Series 982 User’s Manual
Setup Menus, Chapter 4
Program Type
Select whether the program type will be time based or ramp rate.
[``ti] selects a time based program.
[rAtE] selects a program type of ramp rate in degrees or units per
minute.
[PtyP] This prompt always appears.
Default
[``ti] [rAtE]
[PtyP] [PtyP]
Guaranteed Soak Deviation
Guarantees that the process temperature or units is maintained with-
in the selected window centered on the set point. If the process tem-
perature or units varies above or below the set point by more than the
selected value, the time clock stops and the lower display alternately flash-
es [`gSd] and the current parameter until the process variable is again
within the window. Setting [`gSd] to [```0] disables guaranteed soak
deviation.
[`gSd] This prompt always appears.
If Default
↓↓
[``°F] [```0] [`999]
[`C_F] [`gSd] [`gSd]
(Global Menu)
[``°C] [[```0] [``55]
[`C_F] [`gSd] [`gSd]
(Global Menu)
[```0] [`999]
units
a process input [`gSd] [`gSd]
is selected
[`gSd]
Setup-Global