User`s manual

WATLOW Series 982 User’s Manual 4.15
Setup Menus, Chapter 4
Setup-Output
Output 2
Set the way that output 2 will respond to a difference between the set
point and an input variable.
[`AL2] de-energizes output 2 in an alarm condition.
[AL2n] energizes output 2 in an alarm condition.
[``Ht] select reverse action, so that output 2 responds when the input
signal is less than the set point. This prompt only appears if [`Ot1] is set
to [``CL].
[``CL] select direct action, so that output 2 responds when the input
signal is more than the set point. This prompt only appears if [`Ot1] is
set to [``Ht].
[`Ot2] This prompt appears only on controllers equipped with output 2
hardware (not 98__-___A-____). [`AL2] and [AL2n] do not appear if output 2
is a process output (98__-___F-____). [``Ht] and [``CL] do not appear if
[AL90] (in the Global Menu) is set to [dUPL].
Default
[``no] [`AL2] [Al2n] [``Ht] or [``CL]
[`Ot2] [`Ot2] [`Ot2] [`Ot2] [`Ot2]
Process 2
Select the process range for output 2.
[Prc2] This prompt appears only on controllers equipped with output 2
process hardware (98__-___F-____) and with [`Ot2] not set to [``no].
Default
4-20mA 0-20mA 0-5VÎ 1-5VÎ 0-10VÎ (dc)
[4-20] [0-20] [`0-5] [`1-5] [0-10]
[Prc2] [Prc2] [Prc2] [Prc2] [Prc2]
[`Ot2]
[Prc2]
NOTE:
[`Ot2] prompt will
not appear if
[SLid] is selected
for [`In2].