User`s manual

Figure 2.14b Switched DC, Open Collector
98 _ C - _ _ _ _ - _ C _ _
Minimum load resistance: 500
Figure 2.14a AC Outputs
Solid-state Relay with Contact Suppression
98 _ C - _ _ _ _ - _ B _ _
0.5 amps, minimum off-state impedance: 20K
Electromechanical Relay with Contact Suppression
(NO and COM contacts only)
98 _ C - _ _ _ _ - _ D _ _ _
Form C, 5 amps, minimum off-state impedance: 20K
Electromechanical Relay without Contact Suppression
98 _ C - _ _ _ _ - _ E _ _ _
Form C, 5 amps, off-state impedance: 31M
Solid-state Relay without Contact Suppression
98 _ C - _ _ _ _ - _ K _ _ _
0.5 amps, off-state impedance: 31M
2.14 WATLOW Series 982 User’s Manual
Installation and Wiring, Chapter 2
Output 4 Wiring
External 
Load
COM
L
1
L
2
Fuse
NO
5
6
NC
(#7 for D & E outputs only)
7
5
External 
Load
6
+
7
-
COM
Figure 2.14c
External Signal Conditioner Power Supply
98 _ C - _ _ _ _ - _ T _ _
5
6
+
-
+V
-V
Transmitter
4-20mA out
Input 
1 or 2
+
-
For data communications wiring refer to Data Communications
with the Watlow Series 988 Family of Controllers.
˜
NOTE:
Input-to-output iso-
lation is defeated
when the external
transmitter power
supply is used to
power a signal con-
ditioner connected
to input 1.
˜
NOTE:
See Chapter 1 for
power supply DIP
switch information.
˜
NOTE:
Successful installa-
tion requires five
steps:
Model number and
software choice
(Appendix);
DIP switch set-
tings (Chapter 1);
Sensor match
(Chapter 2 and
Appendix);
Sensor installation
(Chapter 2); and
Wiring (Chapter 2).
+ Vdc
Internal Circuitry
5
6
7
790
19 to 32VÎ (dc)