User`s manual

WATLOW Series 982 User’s Manual 2.13
Installation and Wiring, Chapter 2
Figure 2.13c
Process Retransmit
0-20mA, 4-20mA, Load impedance: 600 max.
98 _ C - _ _ _ _ - M _ _ _
0-5V
ÎÎ
, 1-5V
ÎÎ
, 0-10V
ÎÎ
(dc), Load impedance: 500 min.
98 _ C - _ _ _ _ - N _ _ _
˜
NOTE:
Input-to-output iso-
lation is defeated
when the external
signal conditioner
power supply is
used to power a
transmitter con-
nected to input 1.
˜
NOTE:
Successful installa-
tion requires five
steps:
Model number and
software choice
(Appendix);
DIP switch set-
tings (Chapter 1);
Sensor match
(Chapter 2 and
Appendix);
Sensor installation
(Chapter 2); and
Wiring (Chapter 2).
Figure 2.13d External Signal Conditioner Power Supply
98 _ C - _ _ _ _ - T _ _ _
Figure 2.13a AC Outputs
Solid-state Relay with Contact Suppression
98 _ C - _ _ _ _ - B _ _ _
0.5 amps, minimum off-state impedance: 20K
Electromechanical Relay without Contact
Suppression
98 _ C - _ _ _ _ - J _ _ _ _
Form A or B, 5 amps, off-state impedance: 31M
Solid-state Relay without Contact Suppression
98 _ C - _ _ _ _ - K _ _ _ _
0.5 amps, off-state impedance: 31M
External 
Load
COM
L
1
L
2
Fuse
NO Form A
1
2
NC Form B
or
Figure 2.13b Switched DC
98 _ C - _ _ _ _ - C _ _ _
Minimum load resistance: 500
1
2
External 
Load
-
+
1
2
+
-
+V
-V
Transmitter
4-20mA out
Input 
1 or 2
+
-
Form B
Form A
Form A or B
alarm jumper
settings (98_C-
____-J___ only)
+ Vdc
Internal Circuitry
1
2
790
19 to 32VÎ (dc)
1
2
+
-
Output 3 Wiring
˜
NOTE:
See Chapter 1 for
DIP switch location
and settings.