User`s manual
WATLOW Series 982 User’s Manual 7.11
Programming, Chapter 7
By this time you should understand the basic concept of the Series
981/982 and be able to get around on your own. Remember that the
Mode key takes you through the menus and the Up/Down keys select
parameters and values.
1. Return to the Program menu by selecting Prog at the OPEr prompt.
Press the Mode key.
2. Press the Mode key again and select 4 when StEP appears. We are
going to change this step type from an End step to a Set Point step.
This is our second ramp. Use Table 7.11 to enter values into the corre-
sponding parameters.
3. Once you have edited your profile, run it again and watch its progress.
Sample Program
150
125
100
75
50
0
Step 1:
initializes
set point
at 75°F
Step 2:
ramps from
75° to 100°F
Step 3:
a soak step,
holds set
point
Time
(seconds
Temperature
(°F)
Step 5:
a soak step,
holds set
point
Step 4:
ramps from
100° to
Step 6:
jumps to Step 2
and repeats
program a first time
hold mode at
125°F set point
25 50 75 100 125 150 175 200 225 250 275 300
Step 3
Step 4
Step 5
Step 6:
jumps to Step 2
and repeats
program a second time
Step 2
Step 3
Step 4
Step 5
Step 2
Figure 7.11 -
Ramp/Soak with
Jump-loop.
Table 7.11 -
Editing your Profile.
Step #
StyP
Set Point Hour Min SEC Ent3 Ent4 WE WPr JF JS JC
(Step Type)
4 StPt 125 0 0 25 OFF On —————
5 SoAH — 0 0 25 On OFF —————
6 JL———————— 1 2 2