Watlow Series SD ■ 51 ■ Chapter 8 Profiling
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature parame-
ters are in °F through Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer. Decimal
precision is implied at three decimal places unless otherwise noted.
Series SD Profiling Modbus Registers
This section contains information for creating, editing and running profiles using Modbus. Some of these are
available only through Modbus and others can be accessed through the front panel and Modbus. If a parameter is
accessible only through Modbus, N/A appears in the display column. Parameters appear in profiling version only.
[PtYP]
[PtYP]
Profile Type
Set the profile ramp to time based or rate
based.
{~~ti] Time based ramp (0)
{rate] Rate based ramp (1)
[~~ti] (0)
354 R/W
Always
[PStr]
[PStr]
Profile Start
Select where the profile begins the start-
ing set point of the profile, current static
set point or current process temperature.
[`Set]
Static Set Point(0)
[~Pro]
Process (1)
[`Set]
(0)
355 R/W
Always
[Gs;dE]
[gS.dE]
Guaranteed Soak Deviation Enable
Enables the guaranteed soak deviation
function in profiles.
[`~no]
Disabled (0)
[~YES]
Enabled (1)
[~~no]
(0)
356 R/W
Always
[`GSd]
[ gSd]
Guaranteed Soak Deviation Value
Set the value of deviation allowed by the guar-
anteed soak deviation function.
1 to 999
(1 to 999000)
1
*357, 358
R/W
[GS;dE] set to [~YES]
N/A
Profile State
Indicates current profile status.
Profile off (0)
Profile is holding (1)
Profile is running (2)
Pre-run check failed when
starting the profile (3)
Pre-run check failed when
resuming the profle (4)
0
359 R
Available through Mod-
bus only.
N/A
Jump Count Step Enabled
Indicates whether a Jump Step is
currently being executed.
Profile is not running or
profile is running and is not
currently executing a Jump
Step (0)
Profile is running and the
profile is currently execut-
ing a Jump Step (1)
0
363 R
Available through Mod-
bus only.
[File]
[FiLE]
Start File Number
Selects the file to start running.
1 to 4 1
361 R/W
Always
[StEP
]
[StEP]
Start Step Number
Selects the profile step to be run.
1 to 10 1
362 R/W
Always
[SELC]
[SELC]
Profile Select
Selects what to do when a profile is on
hold.
[`Off] Terminate current
profile (0)
[RESU] Resume running
current profile (1)
[hold] Hold current profile
(2)
360 R/W
If profile is holding or
running.
[~gsd]
[ GSd]
Guaranteed Soak Deviation Message
Monitors guaranteed soak deviation
status.
Message Disabled [GSD is
disabled or within range if
enabled. No message is flash-
ing] (0)
Message Enabled [GSD out-
side range and a message is
flashing] (1)
0
364 R
[GS;dE] set to [~YES].
Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if: