User`s manual

Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
Watlow Series SD 44 Chapter 8 Profiling
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature parame-
ters are in °F through Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer. Decimal
precision is implied at three decimal places unless otherwise noted.
[
~~JL] Jump Loop Step
[~~JF]
[ JF]
Jump File
Selects the file which is to be jumped to.
This is a zero-time step.
1 to 4 1
See page
53.
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
[~~JS]
[ JS]
Jump Step
Selects the step which is to be jumped to.
This is a zero-time step.
1 to 10
1
See page
53.
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
[~~JC]
[ JC]
Jump Count
Indicates the number of times the jump
is to be done. A value of 0 results in an
infinite loop.
0 to 9999
1
See page
53.
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
[
Lfil] Link File Step
[~~LF]
[ LF]
Link File
Selects the file to link to.
1 to 4 1
See page
53.
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
[
~End] End Step
[~End]
[ End]
End
Selects the state of the control and auxil-
iary outputs when a profile is ended.
[`OFF] (0)
[hold] (1)
[`OFF] (0)
See page
53.
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )