User`s manual

Watlow Series SD 43 Chapter 8 Profiling
Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature parame-
ters are in °F through Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer. Decimal
precision is implied at three decimal places unless otherwise noted.
[
Soah] Soak Step
[hour]
[hour}
Hours
The number of hours, (plus Min and Sec
parameters) equal the total soak step
time at set point under the [soaH] step
type.
0 to 99 0
See page
53.
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
[Min]
[Min}
Minutes
The number of minutes, (plus Hour and
Sec parameters) equal the total soak step
time at set point under the [soaH] step
type.
0 to 59 0
See page
53.
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
[~SEC]
[ SEC}
Seconds
The number of seconds, (plus Hour and
Min parameters) equal the total soak step
time at set point under the [soaH] step
type.
0 to 59 0
See page
53.
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
[Ent1]
[Ent1}
Event Output 1
Selects whether Event Output 1 is on or
off during the program step.
[`Off] (0)
[``On] (1)
[`Off] (0)
See page
53.
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
Output 1 is set to
[Ent1].
[Ent2]
[Ent2}
Event Output 2
Selects whether Event Output 2 is on or
off during the program step.
[`Off] (0)
[``On] (1)
[`Off] (0)
See page
53.
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
Output 2 is set to
[Ent2].
[Ent3]
[Ent3}
Event Output 3
Selects whether Event Output 3 is on or
off during the program step.
[`Off] (0)
[``On] (1)
[`Off] (0)
See page
53.
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
Output 3 is set to
[Ent3].
[WF;P]
[WF.P}
Wait-for Process Enable
Select to enable Wait-for Process value.
[`~no] (0)
[`YES] (1)
[`~no] (0)
See page
53.
Profiling version only.
[WPr]
[WPr}
Wait-for Process Value
The program will not begin to decrement
the soak time during the programmed
step until process value is equal to the
Wait-for Process Value setting. Once the
Wait-for Process is satisfied, this function
is no longer active for this step.
-1999 to 9999
(-1999000 to 9999000)
75
See page
53.
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )