Watlow Series SD ■ 34 ■ Chapter 5 Setup
Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature parame-
ters are in °F through Modbus.
* Low numbers contain the two lower bytes; high numbers contain the two higher bytes of the four-byte integer. Decimal precision is im-
plied at three decimal places unless otherwise noted.
** Static set point version only (SD_C-_ _ _ _- _ _ _ _ ).
*** Profiling version only (SD_R-_ _ _ _- _ _ _ _ ).
[Addr]
[Addr]
Modbus Device Address
Set the device address for communica-
tions. Every controller on a network must
have a unique address.
1 to 247 1
This can
only be set
from the
controller
front panel.
Output 2 is a communi-
cations output.
(SD_ _ - _ _ U _ - _ _ _ _ )
[bAud]
[bAud]
Baud Rate
Set the baud rate at which the communi-
cations occurs.
[9600]
[`19;2]
[`38;4]
[9600]
This can
only be set
from the
controller
front panel.
Output 2 is a communi-
cations output.
(SD_ _ - _ _ U _ - _ _ _ _ )
[`LOC]
[ LOC]
Lockout
Set the security level for the user inter-
face.
[```0]
(0) no lockout
*** Full profile access.
[```1]
(1) Set Point,
Auto/Manual, alarms only.
*** Full profile access
[```2]
(2) Set Point,
Auto/Manual, only.
*** Pre-Run and Run Menu
access. only. View a running
profile. Profile editing not
permitted.
[```3]
(3) Set Point only
*** Profile access not per-
mitted.
[```4]
(4) full lockout
*** Profile access not per-
mitted.
See the Features Chapter
for details.
[```0]
(0)
43 R/W
Always active.
[`GSd
[ gSd]
Guaranteed Soak Deviation Value***
Set the value of deviation allowed by the
guaranteed soak deviation function.
1 to 999
(1000 to 999000)
1
*357, 358
R/W
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
[GSdE}
is set to [~YES].
[GS;dE]
[gS.dE]
Guaranteed Soak Deviation Enable***
Enables the guaranteed soak deviation func-
tion in profiles.
[`~no]
Disabled (0)
[~YES]
Enabled (1)
[~~no]
(0)
356 R/W
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
[PStr]
[PStr]
Profile Start***
Select where the profile begins the start-
ing set point of the profile, current static
set point or current process temperature.
[`Set]
Static Set Point (0)
[~Pro]
Process (1)
[`Set]
(0)
355 R/W
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
[Ptyp]
[PtyP]
Profile Type***
Set the profile ramp to time based or rate
based.
{~~ti] Time based ramp
(0)
{rate] Rate based ramp
(1)
{~~ti] (0)
354 R/W
Profiling version only.
(SD_ R - _ _ _ _ - _ _ _ _ )
[rP;rt]
[rP.rt]
Ramp Rate**
Set the rate for the set point ramp.
0 to 9999
(0000 to 9999000)
100
*268, 269
R/W
[``rP]
is set to
[`Str]
or
[``On]
.
Does not appear if
[``rP]
is set to
[`OFF]
.
[rP;Sc]
[rP.Sc]
Ramp Scale**
Select the scale of the ramp rate.
[hour]
degrees/hour (0)
[Min]
degrees/minute (1)
[hour]
(0)
267 R/W
[``rP]
is set to
[`Str]
or
[``On]
.