User`s manual

Watlow Series SD 32 Chapter 5 Setup
Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus.All temperature parameters
are in °F through Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer. Decimal
precision is implied at three decimal places unless otherwise noted.
[SiL1]
[SiL1]
Alarm 1 Silencing
Turn alarm silencing on or off.
[`OFF]
off (0) no silencing
[``On]
on (1) silencing
[`OFF]
(0)
109 R/W
[Ot`1]
is set to
[dE;AL]
or
[Pr;AL]
.
[dSP1]
[dSP1]
Alarm 1 Message
Displays an alarm message when an
alarm is active.
[`OFF]
off (0) no message
[``On]
on (1) message
[``On]
(1)
110 R/W
[Ot`1]
is set to
[dE;AL]
or
[Pr;AL]
.
[hyS2]
[hyS2]
Alarm 2 Hysteresis
Set the hysteresis for an alarm. This de-
termines how far into the safe region the
input needs to move before the alarm can
be cleared.
0.0 to 999.0
(0000 to 999000)
1.0
*121, 122
R/W
[Ot`2]
is set to
[dE;AL]
or
[Pr;AL]
.
[Lgc2]
[Lgc2]
Alarm 2 Logic
Select the alarm output condition in the
alarm state.
[AL`C]
closed on alarm (0)
[AL`O]
open on alarm (1)
[AL`C]
(0)
175 R/W
[Ot`2]
is set to
[dE;AL]
or
[Pr;AL]
.
[LAt2]
[LAt2]
Alarm 2 Latching
Turn alarm latching on or off.
[nLAt]
off (0)
[`LAt]
on (1)
[nLAt]
(0)
123 R/W
[Ot`2]
is set to
[dE;AL]
or
[Pr;AL]
.
[SiL2]
[SiL2]
Alarm 2 Silencing
Turn alarm silencing on or off.
[`OFF]
off (0) no silencing
[``On]
on (1) silencing
[`OFF]
(0)
124 R/W
[Ot`2]
is set to
[dE;AL]
or
[Pr;AL]
.
[dSP2]
[dSP2]
Alarm 2 Message
Displays an alarm message when an
alarm is active.
[`OFF]
off (0) no message
[``On]
on (1) message
[``On]
(1)
125 R/W
[Ot`2]
is set to
[dE;AL]
or
[Pr;AL]
.
[hyS1]
[hyS1]
Alarm 1 Hysteresis
Set the hysteresis for an alarm. This de-
termines how far into the safe region the
input needs to move before the alarm can
be cleared.
0.0 to 999.0
(0000 to 999000)
1.0
*106, 107
R/W
[Ot`1]
is set to
[dE;AL]
or
[Pr;AL]
.
[Lgc1]
[Lgc1]
Alarm 1 Logic
Select the alarm output condition in the
alarm state.
[AL`C]
closed on alarm (0)
[AL`O]
open on alarm (1)
[AL`C]
(0)
164 R/W
[Ot`1]
is set to
[dE;AL]
or
[Pr;AL]
.
[LAt1]
[LAt1]
Alarm 1 Latching
Turn J on or off.
[nLAt]
off (0)
[`LAt]
on (1)
[nLAt]
(0)
108 R/W
[Ot`1]
is set to
[dE;AL]
or
[Pr;AL]
.
[r3;;CO]
[r3.CO]
Output 3 Retransmit Offset
Set the offset value for the retransmit
output.
-999.0 to 999.0
(-999000 to 999000)
0
*320, 321
R/W
Output 3 is a process
output (SD_ _ - _ _ _ F -
_ _ _ _ ) and
[Ot`3]
is
set to
[rmt]
.
[r3;;hi]
[r3.hi]
Output 3 Retransmit High Scale
Set the high scale for the retransmit
output.
-1999.0 to 9999.0
(-1999000 to 9999000)
500
*318, 319
R/W
Output 3 is a process
output (SD_ _ - _ _ _ F -
_ _ _ _ ) and
[Ot`3]
is
set to
[rmt]
.
[r3;lo]
[r3.Lo]
Output 3 Retransmit Low Scale
Set the low scale for the retransmit
output.
-1999.0 to 9999.0
(-1999000 to 9999000)
0
*316, 317
R/W
Output 3 is a process
output
(SD_ _ - _ _ _ F -
_ _ _ _ ) and
[Ot`3]
is
set to
[rmt]
.