Watlow Series SD 28 Chapter 5 Setup
Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature parame-
ters are in °F through Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer. Decimal
precision is implied at three decimal places unless otherwise noted.
*** Profiling version only (SD_R-_ _ _ _- _ _ _ _ ).
[sP;hi]
[SP.hi]
Set Point High Limit
Set the high range for the set point.
[rg;Lo]
to max. operating
range (of sensor): if
{`sen}
is set to
{``tc}
[SP;Lo]
+0.100 to 1472: if
{`sen}
is set to
{`rtd}
[SP;Lo]
+0.001 to 9999: if
{`sen}
is set to
[`MA],
[uolt] or [`Mu].
(Set precision with
[P;dEC]
,
Process Decimal Places)
Max. operat-
ing range (J
type):
{``tc}
1472:
{`rtd]
999:
[`MA],
[uolt]
and
[`Mu].
*242, 243
R/W (ther-
mocouple)
*246, 247
R/W (RTD)
*250, 251
R/W (mA, V
or mV)
Always active.
[Ftr;E]
[Ftr.E]
Input Filter
Select filtering action.
[`OFF]
(0) (no filtering)
[DiSP]
(1) (filter only the
display value)
[CntL]
(2) (filter the
control input values)
[both]
(3)
[`OFF] (0)
89 R/W
Always active.
[FLtr]
[FLtr]
Filter Value
Set the input filter value.
0.0 to 60.0 seconds
(0000 to 60000)
0.0
*87, 88
R/W
[Ftr;E] is not set to
[`OFF]
.
[Ot`1]
[Ot 1]
Output 1 Function
Set Output 1 function.
[`OFF]
Off (0)
[Pr;AL]
Process Alarm (1)
[dE;;AL]
Deviation Alarm (2)
[hEAt]
Heat Control (3)
[CooL]
Cool Control (4)
[E;out]
Event (5) ***
[rmt]
Retransmit (6)
[hEAt]
(3)
143 R/W
Always active.
Active only if Output 1
is a process output (SD_
_ - _ F _ _ - _ _ _ _)
[Ctr1]
[Ctr1]
Control Method 1
Set output 1 control type. This parameter
is only used with PID control, but can be
set anytime.
[`Ftb]
Fixed Time Base (0)
[Urtb]
Variable Time Base
(1)
[`Ftb] (0)
144 R/W
[Ot`1]
is set to
[hEAt]
or
[CooL]
and output type
is SD_ _-_ C _ _-_ _ _ _ or
SD_ _-_ K _ _-_ _ _ _.
[Ftb1]
[Ftb1]
Fixed Time Base 1 (Cycle Time)
Set the time base for Fixed Time Base
Control.
1.0 to 60.0 seconds if Out-
put 1 is a mechanical relay
(1000 to 60000)
0.1 to 60.0 seconds if Out-
put 1 is not a mechanical
relay
(100 to 60000)
20.0: mech.
relay
5.0: solid-
state relay
1.0: switched
dc
*145, 146
R/W
[Ot`1]
is set to
[hEAt]
or
[CooL]
,
[Ctr1]
is set
to
[`Ftb]
and Output 1
is not a process output.
(not SD_ _ - _ F _ _ -
_ _ _ _ )
[SP;Lo]
[SP.Lo]
Set Point Low Limit
Set the low range for the set point.
Min. operating range (of
sensor) to
[SP;Hi]
-0.100: if
{`sen}
is set to
{``tc}
-328 to
[SP;hi]
-0.100: if
{`sen] is set to {`rtd}
-1999 to
[SP;hi]
-0.001: if
{`sen}
is set to
[`MA],
[uolt] or [`Mu].
(Set precision with
[P;dEC]
,
Process Decimal Places.)
Min. operat-
ing range (J
type):
{``tc}
-328:
{`rtd}
-999:
[`MA],
[uolt]
and
[`Mu].
*240, 241
R/W (ther-
mocouple)
*244, 245
R/W (RTD)
*248, 249
R/W (mA, V
or mV)
Always active.