User`s manual

Watlow EZ-ZONE
®
ST 86 Appendix
Ordering Information
EZ-ZONE ST Integrated Control Loop
S T
__ __
-
__ __ __ __
-
__ __ __ __
- Output 1 is dedicated to controlling the internal SSR.
- If 75A heat sink is selected below 1 Digital Input (6) will be factory set and fixed as
the SSR over temperature Digital Input.
Output 2, Digital I/O and Current Measurement
K
0.5 A solid-state relay
B
0.5 A solid-state relay with 2 digital i/o points
P
0.5 A solid-state relay with current measurement
E
0.5 A solid-state relay with 2 digital i/o points and current measurement
H
5 A mechanical relay form A
D
5 A mechanical relay form A, 2 digital i/o points
J
5 A mechanical relay form A, current measurement
C
5 A mechanical relay form A, 2 digital i/o points, current measurement
Integrated Limit Controller
1 universal input and 2 outputs
A
None
L
Limit control module (output 3, 5A, Form C mech. relay; output 4, 2A, Form A mech. relay)
B
Terminal block access to mechanical contactor coil contacts
Mechanical Contactor and Power Sup-
ply
If the limit controller was ordered, the contactor will come
internally connected to output 4 on the limit module. The
contactor has external contacts available for daisy chaining to
other branch circuit components.
AH
No contactor and universal high voltage power supply 100 to 240V (ac/dc)
AL
No contactor and universal low voltage power supply 24 to 28V (ac/dc)
B1
Single pole, 40 A Watlow contactor, 24VÅ (ac) power supply
B2
Single pole, 40 A Watlow contactor, 110 / 120VÅ (ac) power supply
B3
Single pole, 40 A Watlow contactor, 208 / 240VÅ (ac) power supply
F1
Dual pole, 40 A Watlow contactor, 24VÅ (ac) power supply
F2
Dual pole, 40 A Watlow contactor, 110 / 120VÅ (ac) power supply
F3
Dual pole, 40 A Watlow contactor, 208 / 240VÅ (ac) power supply
Communications
A
Standard software to connect to pc software, remote user interface (RUI) and other EZ-ZONE devices
M
Modbus™ RTU communication port to connect to non-ST products
Solid-State Relay
B = Zero Cross 10 A, 24 to 240VÅ (ac) output *L = Zero Cross 75A, 48 to 600VÅ (ac) output
C = Zero Cross 25 A, 24 to 240VÅ (ac) output *J = Zero Cross 90A, 48 to 600VÅ (ac) output
D = Zero Cross 40 A, 24 to 240VÅ (ac) output M = Phase Angle 25A, 100 to 240VÅ (ac) output
*E = Zero Cross 50 A, 24 to 240VÅ (ac) output N = Phase Angle 40A, 100 to 240VÅ (ac) output
*K = Zero Cross 75 A, 24 to 240VÅ (ac) output *P = Phase Angle 75A, 100 to 240VÅ (ac) output
*F = Zero Cross 90 A, 24 to 240VÅ (ac) output R = Phase Angle 25A, 260 to 600VÅ (ac) output
G = Zero Cross 25 A, 48 to 600VÅ (ac) output S = Phase Angle 40A, 260 to 600VÅ (ac) output
H = Zero Cross 40 A, 48 to 600VÅ (ac) output *T = Phase Angle 75A, 260 to 600VÅ (ac) output
*EZ-ZONE ST contactor rated @ 40A maximum.
Heat Sinks
A = None (no DIN-rail mount) D = 75A, 24VÎ (dc) fan cooled
B = 25A E = 75A, 115VÅ (ac) fan cooled
C = 40A F = 75A, 240VÅ (ac) fan cooled
Note: If heat sink option D, E or F is selected the integrated PID controller options B, E, D or C must also be ordered.
The 75A heat sink includes an SSR over-temperature thermostat shut-down feature factory connected to Digital Input 6.
Firmware
A
Standard Watlow
P
Profile ramp and soak (4 profiles, 40 steps)
S
Custom
Customization (logo, parameters, hardware, firmware)
AA
Standard
XX
{letters to be determined, consult factory}
Model Numbers for EZ-ZONE
®
ST