User`s manual

Watlow EZ-ZONE
®
ST 60 Chapter 6 Factor y Page
Control Module Factory Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[CUSt]
[FCty]
Custom Setup Menu
[`par]
[ Par]
Custom
Parameter 1 to 20
Select the parameters
that will appear in the
Home Page.
The Parameter 1 value
will appear in the
upper display of the
Home Page. It cannot
be changed with the
Up and Down Keys
in the Home Page.
The Parameter 2 value
will appear in the
lower display in the
Home Page. It can
be changed with the
Up and Down Keys,
if the parameter is a
writable one.
Scroll through the
other Home Page
parameters with the
Advance Key
.
[nonE] None (61)
[`l;st] Limit Status (1668)
[`L;hy] Limit Hysteresis (183)
[`Lh;S] Limit High Set Point (182)
[`LL;S] Limit Low Set Point (181)
[`CU;r] Sensed Current (179)
[gSd1] Guaranteed Soak Deviation
1 Value (1214)
[P;ACr] Profile Action Request (109)
[P;Str] Profile Start (79)
[idLE] Idle Set Point (107)
[t;tUn] TRU-TUNE+
®
Enable (205)
[`r;rt] Ramp Rate (177)
[`C;hy] Cool Hysteresis (170)
[`C;Pb] Cool Proportional Band
(169)
[`h;hy] Heat Hysteresis (167)
[`h;Pb] Heat Proportional Band
(166)
[``db] Dead Band (164)
[``td] Time Derivative (163)
[``ti] Time Integral (162)
[`C;Pr] Cool Power (161)
[`h;Pr] Heat Power (160)
[`C;M] User Control Mode (159)
[`AUt] Autotune (158)
[``op] Open Loop Set Point (110)
[AC;SP] Active Set Point (72)
[AC;pu] Active Process Value (25)
[StPt] Set Point (85)
CUSt] Custom Menu (180)
[`A;hy] Alarm Hysteresis (97)
[`A;hi] Alarm High Set Point (78)
[`A;Lo] Alarm Low Set Point (42)
[USr;r] User Restore Set (1171)
[`C_F] Display Units (156)
[`i;CA] Input Calibration Offset
(154)
[`Pro] Process (75)
See:
Home
Page
Instance 1
Map 1 Map 2
- - - - - - - -
- - - - 14005
uint
RWES
[`iid]
[ iid]
Custom (1 to 20)
Instance ID
Select the parameters
that will appear in the
Home Page.
1 to 2 - - - -
Instance 1
Map 1 Map 2
- - - - - - - -
- - - -
- - - - 14003
uint
RWES
[`LoC]
[FCty]
Security Setting Menu
[LoC;o]
[LoC.o]
Security Setting
Operations Page
Change the security
level of the Opera-
tions Page.
1 to 3 2
Instance 1
Map 1 Map 2
- - - - 1692
- - - - - - - - 3002 - - - -
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with another interface.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EE-
PROM
S: User
Set