User`s manual

Watlow EZ-ZONE
®
ST 52 Chapter 4 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which scale to use
for temperature.
[```F] °F (30)
[```C] °C (15)
°F Instance 1
Map 1 Map 2
- - - - 1698
- - - - 110 3005 - - - - uint
RWES
[AC;LF]
[AC.LF]
Global
AC Line Frequency
Set the frequency to the
applied ac line power
source.
[``50] 50 Hz (3)
[``60] 60 Hz (4)
60 Hz Instance 1
Map 1 Map 2
129 946
0x65 (101)
1
0x22 (34)
- - - - 1034 Inst. 1
886
uint
RWES
[P;typ]
[P.tyP]
Global
Profile StartType
Set the profile startup to
be based on a set point or
a process value.
[StPt]Set Point (85)
[`Pro]Process (75)
Set Point Instance 1
Map 1 Map 2
302 3814
0x7A
(122)
1
8
- - - - 22008 Inst. 1
2914
uint
RWE
[`GSE]
[ gSE]
Global
Guaranteed Soak En-
able
Enables the guaranteed
soak deviation function in
profiles.
[`oFF] Off (62)
[``on] On (63)
Off Instance 1
Map 1 Map 2
299 3810
0x7A
(122)
1
6
- - - - 22006 Inst. 1
2910
uint
RWE
[GSd1]
[gSd1]
Global
Guaranteed Soak De-
viation 1
Set the value of the de-
viation band that will be
used in all profile step
types. The process value
must enter the deviation
band before the step can
proceed.
0.0 to 9,999.000°F or units
0.0 to 5,555.000°C
10.0°F or
units
6.0°C
Instance 1
Map 1 Map 2
300 3812
0x7A
(122)
1
7
- - - - 22007 Inst. 1
2912
float
RWE
No Dis-
play
Global
Ramping Type
Defines whether profiles
will use time or rate
Rate (81)
Time (143)
Time Instance 1
Map 1 Map 2
- - - - 3874
0x7A
(122)
1
0x26 (38)
- - - - 22038 Inst. 1
- - - -
uint
RWE
[d;prs]
[d.PrS]
Global
Display Pairs
Defines the number of
Display Pairs.
1 to 10 2 Instance 1
Map 1 Map 2
- - - - 1744
- - - - - - - - 3028 - - - - uint
RWES
[USr;S]
[USr.S]
Global
User Settings Save
Save all of this control-
ler's settings to the se-
lected set.
[SEt1] User Set 1 (101)
[SEt2] User Set 2 (102)
[none] None (61)
None
Instance 1
Map 1 Map 2
17 26
0x(101)
1
0xE (14)
118 1014
Inst. 1
26
uint
RWE
[USr;r]
[USr.r]
Global
User Restore Settings
Replace all of this con-
troller's settings with
another set.
[FCty] Factory (31)
[none] None (61)
[SEt1] User Set 1 (101)
[SEt2] User Set 2 (102)
None
Instance 1
Map 1 Map 2
16 24
0x65
(101)
1
0xD (13)
117 1013
Inst. 1
24
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EE-
PROM
S: User