User`s manual
Watlow EZ-ZONE
®
ST • 41 • Chapter 4 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[`S;Lo]
[ S.Lo]
Analog Input (1 to 2)
Scale Low
Set the low scale for pro-
cess inputs. This value,
in millivolts, volts or mil-
liamps, will correspond to
the Range Low output of
this function block.
-100.0 to 1,000.0 0.0 Instance 1
Map 1 Map 2
57 388
Instance 2
Map 1 Map 2
85 478
0x68 (104)
1 to 2
0xF (15)
6 4015 Inst. 1
388
Inst. 2
548
float
RWES
[`S;hi]
[ S.hi]
Analog Input (1 to 2)
Scale High
Set the high scale for
process inputs. This value,
in millivolts, volts or mil-
liamps, will correspond to
the Range High output of
this function block.
-100.0 to 1,000.0 20.0 Instance 1
Map 1 Map 2
59 390
Instance 2
Map 1 Map 2
87 480
0x68 (104)
1 to 2
0x10 (16)
7 4016 Inst. 1
390
Inst. 2
550
float
RWES
[`r;Lo]
[ r.Lo]
Analog Input (1 to 2)
Range Low
Set the low range for this
function block's output.
-1,999.000 to 9,999.000 0.0 Instance 1
Map 1 Map 2
61 392
Instance 2
Map 1 Map 2
89 482
0x68 (104)
1 to 2
0x11 (17)
8 4017 Inst. 1
392
Inst. 2
552
float
RWES
[`r;hi]
[ r.hi]
Analog Input (1 to 2)
Range High
Set the high range for this
function block's output.
-1,999.000 to 9,999.000 9,999 Instance 1
Map 1 Map 2
63 394
Instance 2
Map 1 Map 2
91 484
0x68 (104)
1 to 2
0x12 (18)
9 4018 Inst. 1
394
Inst. 2
554
float
RWES
[`P;EE]
[ P.EE]
Analog Input (1 to 2)
Process Error Enable
Turn the Process Error
Low feature on or off.
[`off] Off (62)
[Low] Low (53)
Off Instance 1
Map 1 Map 2
- - - - 418
Instance 2
Map 1 Map 2
- - - - 508
0x68 (104)
1 to 2
0x1E (30)
10 4030 - - - - uint
RWES
[`P;EL]
[ P.EL]
Analog Input (1 to 2)
Process Error Low
If the process value drops
below this value, it will
trigger an input error.
-100.0 to 1,000.0 0.0 Instance 1
Map 1 Map 2
- - - - 420
Instance 2
Map 1 Map 2
- - - - 510
0x68 (104)
1 to 2
0x1F (31)
11 4031 - - - - float
RWES
[`FiL]
[ FiL]
Analog Input (1 to 2)
Filter
Filtering smooths out the
process signal to both the
display and the input.
Increase the time to in-
crease filtering.
0.0 to 60.0 seconds 0.5 Instance 1
Map 1 Map 2
55 386
Instance 2
Map 1 Map 2
83 476
0x68 (104)
1 to 2
0xE (14)
12 4014 Inst. 1
386
Inst. 2
546
float
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EE-
PROM
S: User
Set