User`s manual
Watlow EZ-ZONE
®
ST • 40 • Chapter 4 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[``Ai]
[`Set]
Analog Input Menu
[`Sen]
[ SEn]
Analog Input (1 to 2)
Sensor Type
Set the analog sensor type
to match the device wired
to this input.
Note:
There is no open-
sensor detection
for process inputs.
[`oFF] Off (62)
[``tC] Thermocouple (95)
[`mu] Millivolts (56)
[uolT] Volts dc (104)
[`MA]
Milliamps dc (112)
[r0;1H] RTD 100 Ω (113)
[r1;0H] RTD 1,000 Ω (114)
Instance 1
Map 1 Map 2
42 368
Instance 2
Map 1 Map 2
70 458
0x68 (104)
1 to 2
5
3 4005 Inst. 1
368
Inst. 2
528
uint
RWES
[`Lin]
[ Lin]
Analog Input (1 to 2)
Linearization
Set the linearization to
match the thermocouple
wired to this input.
[```J] J (46)
[```F] F (30)
[```E] E (26)
[```d] D (23)
[```C] C (15)
[```b] B (11)
[```t] T (93)
[```S] S (84)
[```r] R (80)
[```n] N (58)
[```H] K (48)
J
Instance 1
Map 1 Map 2
43 370
Instance 2
Map 1 Map 2
71 460
0x68 (104)
1 to 2
6
4 4006 Inst. 1
370
Inst. 2
530
uint
RWES
[`Rt;L]
[ rt.L]
Analog Input (1 to 2)
RTD Leads
Set to match the number
of leads on the RTD wired
to this input.
[```2] 2 (1)
[```3] 3 (2)
2 Instance 1
Map 1 Map 2
44 372
Instance 2
Map 1 Map 2
72 462
0x68 (104)
1 to 2
7
- - - - 4007 Inst. 1
372
Inst. 2
532
uint
RWES
[Unit]
[Unit]
Analog Input (1 to 2)
Units
Set the type of units the
sensor will measure.
[`A;tP] Absolute Temperature
(1540)
[``rh] Relative Humidity
(1538)
[`Pro] Process (75)
[PWr] Power (73)
Process Instance 1
Map 1 Map 2
- - - - 442
Instance 2
Map 1 Map 2
- - - - 532
0x68 (104)
1 to 2
0x2A (42)
5 4042 - - - - uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EE-
PROM
S: User
Set
To go to the Setup Page from the Home Page, press both
the Up ¿ and Down ¯ keys for six seconds. [``Ai] will
appear in the upper display and [`Set] will appear in
the lower display.
• Press the Up ¿ or Down ¯ key to move through
the menus.
• Press the Advance Key
‰
to move to a submenu.
• Press the Up ¿ or Down ¯ key to move through
the submenus.
• Press the Advance Key
‰
to move through the pa-
rameters of the menu or submenu.
• Press the Infinity Key ˆ to move backwards
through the levels: parameter to submenu; sub-
menu to menu; menu to Home Page.
• Press and hold the Infinity Key ˆ for two seconds
to return to the Home Page.
Note:
Avoid continuous writes within loops. Excessive writes to EEPROM
will cause premature EEPROM failure. The EEPROM is rated for
1,000,000 writes. Navigate to Setup Page under the CoM menu and
set prompt Non-volatile Save [`nU;S] to No.