User`s manual
17
18
19
20
Setup Menu
16
th
& 32
nd
DIN PID Controller
Display Parameter Name Description Range (Defaults are shown bold)
[``rP]
[ rP]
Ramp Action
Select when the controller's set point will ramp to the defined end set point.
Appears if: Always
[`oFF] Off
[`Str] Startup
[StPt] Set Point Change
[both] Both
[`r;rt]
[ r.rt]
Ramp Rate
Set the rate for the set point ramp. Set the time units for the rate with the Ramp
Scale parameter.
Appears if: Ramp Action is set to Startup, Set Point or Both.
1.0°F degrees or units per hour
1.0°C
[o;hi1]
[o.hi1]
Power Scale Output High 1
Set maximum value of output 1 range.
Appears if: Output 1 is set to heat
0.0 to 100%
100.0
[o;hi2]
[o.hi2]
Power Scale Output High 2
Set maximum value of output 2 range.
Appears if: Output 2 is set to heat
0.0 to 100%
100.0
[PAr1]
[PAr1]
Upper or Left Display
Select parameter to display.
Appears if: Always
[AC;Pu]
Active Process Value
[none] none
[PAr2]
[PAr2]
Lower or Right Display
Select parameter to display.
Appears if: Always
[AC;SP]
Active Set Point
[`A;hi]
Alarm High Set Point
[`A;Lo]
Alarm Low Set Point
[none] None
[`ad;s]
[ Ad.S]
Zone Address - Standard Bus Communication
Set zone address from 1-16.
Appears if: Always
1-16
1
Setup Menu
16
th
& 32
nd
DIN PID Controller
Display Parameter Name Description Range (Defaults are shown bold)
[`fn2]
[ fn2]
Function of Output 2
Select which function will drive this output.
Appears if: If output 2 is ordered
[`oFF] Off
[CooL] Cool
[hEAt] Heat
[ALM] Alarm
[`h;Ag]
[ h.Ag]
Heat Algorithm
Set the heat control method.
Appears if: Output 1 or 2 set to heat
[`oFF] Off
[`Pid] PID
[on;of] On-Off
[`hSC]
[ hSC]
Hysteresis (Heat & Cool)
Set the control switching hysteresis for on-off control. This determines how far into
the “on” region the process value needs to move before the output turns on.
Appears if: Heat or Cool Algorithm is set to On-Off.
0 to 9,999.000°F or units
0 to 5,555.000°C
Units, 3.0°F or 2.0°C
[`C;Ag]
[ C.Ag]
Cool Algorithm
Set the cool control method.
Appears if: If Output 1 or 2 is set to cool
[`oFF] Off
[`Pid] PID
[on;of] On-Off
[`A;ty]
[ A.ty]
Alarm Type
Select how the alarm will or will not track the set point.
Appears if: Always
[`oFF] Off
[PR;AL] Process Alarm
[dE;AL] Deviation Alarm
[`A;hy]
[ A.hy]
Alarm Hysteresis
Set the hysteresis for an alarm. This determines how far into the safe region the
process value needs to move before the alarm can be cleared.
Appears if: When alarm type is set to process or deviation alarm
0.001 to 9,999.000°F or units
0.001 to 5,555.000°C
Units, 1.0°F or 1.0°C
[`A;LA]
[ A.LA]
Alarm Latching
Turn alarm latching on or off. A latched alarm has to be turned off by the user.
Appears if: When alarm type is set to process or deviation alarm
[nLAt] Non-Latching
[`LAt] Latching
[`A;bL]
[ A.bL]
Alarm Blocking
Select when an alarm will be blocked. After startup and/or after the set point chang-
es, the alarm will be blocked until the process value enters the normal range.
Appears if: When alarm type is set to process or deviation alarm
[`oFF] Off
[`Str] Startup
[StPt] Set Point
[both] Both
[`A;si]
[ A.Si]
Alarm Silencing
Turn alarm silencing on to allow the user to disable the output tied (configured) to
this alarm
Appears if: When alarm type is set to process or deviation alarm
[`oFF] Off
[``on] On
[A;dSP]
[A.dSP]
Alarm Display
Display an alarm message when an alarm is active.
Appears if: When alarm type is set to process or deviation alarm
[`oFF] Off
[``on] On
‰
[`loC] Lockout Menu
[`SEn] Sensor Type
[`Lin] Linearization
[`deC] Decimal
[`C_F] Display Units
[`r;lo] Range Low
[`r;hi] Range High
[`fn1] Function One
[`o;ty] Output Type
[`fn2] Function Two
[`h;ag] Heat Algorithm
[`h;sC] Heat Hysteresis
[`C;Ag] Cool Algorithm
[`A;ty] Alarm Type
[`A;hy] Alarm Hysteresis
[`A;lA] Alarm Latching
[`A;bl] Alarm Blocking
[`A;si] Alarm Silencing
[A;dsp] Alarm Display
[``rp] Ramp Action
[`r;rt] Ramp Rate
[o;hi1] Power Scale High Output 1
[o;hi2] Power Scale High Output 2
[par1] Upper or Left Display
[par2] Lower or Right Display
[`Ad;s] Zone Address
Setup Menu
‰
[`loC] Lockout Menu
[`SEn] Sensor Type
[`Lin] Linearization
[`deC] Decimal
[`C_F] Display Units
[`r;lo] Range Low
[`r;hi] Range High
[`fn1] Function One
[`o;ty] Output Type
[`fn2] Function Two
[`h;ag] Heat Algorithm
[`h;sC] Heat Hysteresis
[`C;Ag] Cool Algorithm
[`A;ty] Alarm Type
[`A;hy] Alarm Hysteresis
[`A;lA] Alarm Latching
[`A;bl] Alarm Blocking
[`A;si] Alarm Silencing
[A;dsp] Alarm Display
[``rp] Ramp Action
[`r;rt] Ramp Rate
[o;hi1] Power Scale High Output 1
[o;hi2] Power Scale High Output 2
[par1] Upper or Left Display
[par2] Lower or Right Display
[`Ad;s] Zone Address
Setup Menu
To enter the Setup Menu push and hold
the up and down arrow keys for ap-
proximately 3 seconds. Once there, push
the green advance key to scroll through
to the prompt of choice and then use
the up and down arrow keys to change
the range. At any point within the Setup
menu to return to the default display
push the Infi nity
ˆ key.
To enter the Setup Menu push and hold
the up and down arrow keys for ap-
proximately 3 seconds. Once there, push
the green advance key to scroll through
to the prompt of choice and then use
the up and down arrow keys to change
the range. At any point within the Setup
menu to return to the default display
push the Infi nity
ˆ key.