User`s manual

Setup Menu
16
th
& 32
nd
DIN PID Controller
Display Parameter Name Description Range (Defaults are shown bold)
LoC
[LoC]
Lockout Menu
Set the security clearance level. The user can access the selected level and all
lower levels.
Appears if: Always
1 to 5
1 Operations Menu (read only, A/M button disabled)*
2 Operations Menu (A/M button disabled, Set point R/W)*
3 Operations Menu (A/M button enabled, Set point R/W, Control
Mode R/W)*
4 Operations Menu R/W access*
5 Operations Menu and Setup Menu full R/W access
*You can change the security level at any level
[Sen]
[ SEn]
Sensor Type
Set the analog sensor type to match the device wired to this input.
Appears if: Always
[``tC] Thermocouple
[uolT] Volts dc
[`MA]
Milliamps dc
[r0;1H] RTD 100 Ω
[Lin]
[ Lin]
Linearization
Set the linearization to match the thermocouple type wired to this input.
For example, select [```H] for a type K thermocouple.
Appears if: Sensor Type is set to Thermocouple.
[`J] J
[`H] K
[`n] N
[`S] S
[`t] T
[`dEC]
[ dEC]
Decimal
Set the precision of the displayed value.
Appears if: Always
[```0] Whole
[``0;0] Tenths
[`0;00] Hundredths
[`C_F]
[ C_F]
Display Units
Select which units will be displayed.
Appears if: Always
[```F] °F
[```C] °C
[r;Lo]
[ r.Lo]
Range Low
Set the low range of the set point.
Appears if: Always
-1,999.000 to 9,999.000
0.0
[rhi]
[ r.hi]
Range High
Set the high range of the set point.
Appears if: Always
-1,999.000 to 9,999.000
[`fn1]
[ fn1]
Function of Output 1
Select which function will drive this output.
Appears if: If output 1 is ordered
[`oFF] Off
[CooL] Cool
[hEAt] Heat
[ALM] Alarm
[`o;ty]
[ o.ty]
Output Type
Select whether the process output will operate in volts or milliamps.
Appears if: A process output (PM _ C _ F _-_ AAAB _ _)
[uoLt] Volts
[`MA] Milliamps
Operations Menu
16
th
& 32
nd
DIN PID Controller
Display Parameter Name Description Range (Defaults are shown bold)
[`AUt]
[ AUt]
Autotune
Start an autotune. While active the upper or left and lower or right display will
flash tUn1 and Attn.
Appears if: Heat or cool algorithm set to PID
[``no] No
[`yES] Yes
[`C;M]
[ C.M]
Control Mode Active
View the current control mode.
Appears if: Always
[`off] Off
[AUto] Auto
[MAn] Manual
[`h;Pb]
[ h.Pb]
Heat Proportional Band
Set the PID proportional band for the heat outputs.
Appears if: Heat algorithm set to PID
0 to 9,999.000°F or units
0 to 5,555.000°C
Units, 25.0°F or 14.0°C
[`C;Pb]
[ C.Pb]
Cool Proportional Band
Set the PID proportional band for the cool outputs.
Appears if: Cool algorithm set to PID
0 to 9,999.000°F or units
0 to 5,555.000°C
Units, 25.0°F or 14.0°C
[``ti]
[ ti]
Time Integral
Set the PID integral for the outputs.
Appears if: Heat or cool algorithm set to PID
0 to 9,999 seconds per repeat
180.0
[``td]
[ td]
Time Derivative
Set the PID derivative time for the outputs.
Appears if: Heat or cool algorithm set to PID
0 to 9,999 seconds
0.0 seconds
[o;tb1]
[o.tb1]
Time Base Output 1
Set the time base for fixed-time-base control.
Appears if: Output 1 set to heat or cool with control algorithm set to PID.
0.1 to 60.0 seconds (solid-state relay or switched dc)
5.0 to 60.0 seconds (mechanical relay & NO-ARC power control)
1 sec. [SSR & sw dc], 20.0 sec. [mech. relay & NO-ARC]
[o;tb2]
[o.tb2]
Time Base Output 2
Set the time base for fixed-time-base control.
Appears if: Output 2 set to heat or cool with control algorithm set to PID.
0.1 to 60.0 seconds (solid-state relay or switched dc)
5.0 to 60.0 seconds (mechanical relay & NO-ARC power control)
1 sec. [SSR & sw dc], 20.0 sec. [mech. relay & NO-ARC]
[`A;Lo]
[ A.Lo]
Alarm Low Set Point
Process - set the process value that will trigger a low alarm.
Deviation - set the span of units from the closed loop set point that will trigger
a low alarm.
Appears if: If Alarm Type (A.ty) is set to Process or Deviation Alarm
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 32.0°F or 0.0°C
[`A;hi]
[ A.hi]
Alarm High Set Point
Process - set the process value that will trigger a high alarm.
Deviation - set the span of units from the closed loop set point that will trigger
a high alarm.
Appears if: If Alarm Type (A.ty) is set to Process or Deviation Alarm
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 300.0°F or 150.0°C
[`i;CA]
[ i.CA]
Calibration Offset
Set an offset value for a process output.
Appears if: Always
-1,999.000 to 9,999.000°F or units
-1,110.555 to 5,555.000°C
0.0
[`AUt] Autotune
[`C;M] Control Mode
[`h;pb] Heat Proportional Band
[`C;pb] Cool Proportional Band
[``ti] Time Integral
[``td] Time Derivative
[o;tb1] Time Base
[o;tb2] Time Base
[`A;lo] Alarm Low Set Point
[`A;hi] Alarm High Set Point
[`i;Ca] Calibration Offset
Operations Menu
[`loC] Lockout Menu
[`SEn] Sensor Type
[`Lin] Linearization
[`deC] Decimal
[`C_F] Display Units
[`r;lo] Range Low
[`r;hi] Range High
[`fn1] Function One
[`o;ty] Output Type
[`fn2] Function Two
[`h;ag] Heat Algorithm
[`h;sC] Heat Hysteresis
[`C;Ag] Cool Algorithm
[`A;ty] Alarm Type
[`A;hy] Alarm Hysteresis
[`A;lA] Alarm Latching
[`A;bl] Alarm Blocking
[`A;si] Alarm Silencing
[A;dsp] Alarm Display
[``rp] Ramp Action
[`r;rt] Ramp Rate
[o;hi1] Power Scale High Output 1
[o;hi2] Power Scale High Output 2
[par1] Upper or Left Display
[par2] Lower or Right Display
[`Ad;s] Zone Address
Setup Menu
Upon power up of the control, using
the advance key will scroll through the
various prompts found in the Operations
Menu. At any point within the Operations
menu to return to the default display
push the Infi nity ˆ key.
To enter the Setup Menu push and hold
the up and down arrow keys for ap-
proximately 3 seconds. Once there, push
the green advance key to scroll through
to the prompt of choice and then use
the up and down arrow keys to change
the range. At any point within the Setup
menu to return to the default display
push the Infi nity
ˆ key.
13 14
15 16