User`s manual

9
10
11
12
Note:
In the drawings below for each input notice that the Slot A connector labeling is identified.
Note:
When using a 2 wire RTD, jumper S1 and T1 together
Inputs
All inputs shown below represent input 1 (the only input) and are to be connected to slot A of the PID
Control.
Process Volts and Amperes
4 to 20 mA @ 100 Ω input impedance
0 to 10VÎ (dc) @ 20 kΩ input impedance
• Scalable
Resistance Temperature Detector (RTD)
Platinum, 100 Ω @ 0°C
Calibration to DIN curve (0.00385 Ω/Ω/°C)
20 Ω total lead resistance
RTD excitation current of 0.09 mA typical.
Each ohm of lead resistance may affect the
reading by 0.03°C.
For 3-wire RTDs, the S1 lead must be con-
nected to R1.
For best accuracy use a 3-wire RTD to com-
pensate for lead-length resistance. All three
lead wires must have the same resistance.
Thermocouple
2 KΩ maximum source resistance
>20 MΩ input impedance
3 microampere open-sensor detection
Thermocouples are polarity sensitive. The
negative lead must be connected to S1.
To reduce errors, the extension wire for ther-
mocouples must be of the same alloy as the
thermocouple.
-
+
Thermocouple
S1
R1
T1
S1
R1
S1
S2
S3
RTD
2 or 3 Wire
-
+
-
+
S1
R1
T1
S1
Process
Volts
Process
Amperes
Power Supply Note:
Switched dc and Process outputs use a common power supply with a maximum current output of 40mA.
As an example, supplied current (mA) from output 1 and 2 can be 20/20, 30/10, 40/0, 10/30, etc...
Outputs
Please note all outputs are connected exclusively to slot A. Output availability is based on the part number
of your PID Control.
Quencharc Note:
Switching pilot duty inductive loads (relay coils, solenoids, etc.) with
the mechanical relay, solid state relay or open collector output op-
tions requires use of an R.C. suppressor.
F1
H1
G1
negative
volts +
current +
4
Universal Process
PM _ (C) _ F _ - A A A A B _ _
L2
K2
NO-ARC Relay
Form A
PM _ (C) _ _ H - A A A A B _ _
Open Collector
Load
Power
Supply
dc -
common
X1
W1
PM _ (C) _ C _ - A A A A B _ _
L1
J1
K1
normally open
common
normally closed
Mechanical Relay
Form C
PM _ (C) _ E _ - A A A A B _ _
Solid-State Relay
Form A
L1 and/or L2
K1 and/or K2
PM _ (C) _ K K - A A A A B _ _
W1 and/or W2
dc +
dc -
Y1 and/or Y2
common
Switched DC
PM _ (C) _ C C - A A A A B _ _
L2
K2
Mechanical Relay
Form A
PM _ (C) _ _ J - A A A A B _ _
Switched DC
Supplied current up to a maximum of 40 mA.
See Power Supply note above.
Short circuit limited to <50 mA
22 to 32VÎ (dc) open circuit voltage
Use dc- and dc+ to drive external solid-state
relay.
• DIN-A-MITE compatible
- single-pole: up to 4 in parallel or 4 in series
- 2-pole: up to 2 in parallel or 2 in series
- 3-pole: up to 2 in series
Open Collector
100 mA maximum output current sink
• 30VÎ (dc) maximum supply voltage
Any switched dc output can use the common
terminal.
Use an external power supply to control a dc
load, with the load positive to the positive of
the power supply, the load negative to the
open collector and common to the power sup-
ply negative.
See Quencharc note.
Mechanical Relay Form C
5 A at 240VÅ (ac) or 30VÎ (dc) maximum
resistive load
20 mA at 24V minimum load
125 VA pilot duty at 120/240VÅ (ac), 25 VA at
24VÅ (ac)
100,000 cycles at rated load
Output does not supply power.
For use with ac or dc
See Quencharc note.
Mechanical Relay Form A
5 A at 240VÅ (ac) or 30VÎ (dc) maximum
resistive load
20 mV at 24V minimum load
125 VA pilot duty @ 120/240VÅ (ac), 25 VA at
24VÅ (ac)
100,000 cycles at rated load
Output does not supply power.
For use with ac or dc
See Quencharc note.
NO-ARC Relay Form A
15 A at 85 to 264VÅ (ac) resistive load only
1/16 DIN models only
2,000,000 cycle rating for NO-ARC circuit
100 mA minimum load
2 mA maximum off state leakage
Do not use on dc loads.
Output does not supply power.
Solid-State Relay Form A
0.5 A at 20 to 264VÅ (ac) maximum resistive
load
20 VA 120/240VÅ (ac) pilot duty
Opto-isolated, without contact suppression
Maximum off state leakage of 105 microam-
peres
Output does not supply power
Do not use on dc loads.
See Quencharc note.
Universal Process
4 to 20 mA into 800 Ω maximum load
0 to 10VÎ (dc) into voltage 1 kΩ minimum
load
• Scalable
Output supplies power (See Power Supply
note above).
Cannot use voltage and current outputs at
same time
Upper Display:
In the Operations Menu,
displays the process
value, otherwise displays
the value of the param-
eter in the lower display.
Zone Display:
When 2onE (found in the
Factory Page) is set to on, indi-
cates the controller zone.
1 to 9 = zones 1 to 9
A = zone 10 E = zone 14
b = zone 11 F = zone 15
C = zone 12 h = zone 16
d = zone 13
Lower Display:
Indicates the set point or output
power value during operation,
or the parameter whose value
appears in the upper display.
A/M Key:
This key will toggle the control
mode between the current value of
the C.M prompt (Off, MAn, AUto)
and Manual when the A/M button
is pushed and held for 3 seconds.
Infinity Key: ˆ
Clears and Silences alarms, press
to back up one level, or press and
hold for two seconds to return to
the Operations Menu.
Temperature Units Indicator
Lights:
Indicates whether the tempera-
ture is displayed in Fahrenheit
or Celsius.
Output Activity:
Number lights indicate activity of
outputs 1 and 2.
Percent Units Indicator:
Lights when the controller is
displaying values as a percentage
or when the open-loop set point
is displayed.
Communications Activity:
Flashes when another device
is communicating with this
controller.
Up and Down Keys: ¿ ¯
In the Operations Menu, adjusts the
set point in the lower display. In other
pages, changes the upper display to
a higher or lower value, or changes a
parameter selection.
®
M
A
Keys & Displays
16
th
DIN PID Controller
Advance Key:
Advances through
parameter
prompts.
An active message will cause the display to toggle
between the normal settings and the active mes-
sage in the upper or left display and [Attn] in the
lower or right display. Your response will depend
on the message and the controller settings. Some
messages, such as Tuning, indicate that a process
is underway. If a message is generated in the
right or lower display that can be cleared (such
as [AL;h1]), simply push the infinity ˆ key to
execute the action ([CLr]).
[AL;L1] Alarm Low 1
[AL;h1] Alarm High 1
[AL;E1] Alarm Error 1
[Er;i1] Error Input 1
[tUn1] Tuning
[`rP1] Ramping
Left Display:
In the Operations Menu, displays
the process value, otherwise dis-
plays the value of the parameter
in the left display.
%
2
1
®
With a few exceptions, all of the key functions described for the 16
th
DIN PID Controller apply to the 32
nd
DIN PID Controller as well.
Right Display:
Indicates the set point or output
power value during operation,
or the parameter whose value
appears in the right display.
32
nd
DIN PID Controller
Responding to a Displayed Message (16
th
or 32
nd
DIN)