User`s manual

Installation
RETENTION COLLAR
CASE
PANEL
BEZEL
GASKET
1. Make the panel cutout using the mounting
template dimensions in this chapter. Insert the
case assembly into the panel cutout.
2. While pressing the case assembly firmly
against the panel, slide the mounting collar
over the back of the controller.
If the installation does not require a NEMA 4X
seal, slide the mounting collar up to the back of
the panel tight enough to eliminate the spacing
between the gasket and the panel.
Slide the mounting col-
lar over the back of the
controller.
Place the blade of a
screwdriver in the
notch of the mount-
ing collar assembly.
3. For a NEMA 4X seal, place the blade of a
screwdriver in the notch of the mounting collar
assembly and push toward the panel while
applying pressure to the face of the controller.
Don't be afraid to apply enough pressure to
properly install the controller.
The seal system is compressed more by mat-
ing the mounting collar tighter to the front
panel (see picture). If you can move the case
assembly back and forth in the cutout, you do
not have a proper seal. The tabs on each side
of the mounting collar have teeth that latch into
the ridges on the sides of the controller. Each
tooth is staggered at a different depth from the
front so that only one of the tabs, on each side,
is locked onto the ridges at a time.
BEZEL
PANEL
CASE
COLLAR
RETENTION
GASKET
Removing the Mounted Controller from Its Case
1. From the controller's face, pull out the tab on
each side until you hear it click.
Pull out the tab on
each side until you
hear it click.
Grab the unit above
and below the face
and pull forward.
2. Once the sides are released, grab the unit
above and below the face with two hands and
pull the unit out. If it is difficult to pull the unit
out, remove the connectors from the back of
the controller. This should make it easier to
remove.
Ó Warning:
All electrical power to the controller and con-
trolled circuits must be disconnected before
removing the controller from the front panel
or disconnecting other wiring. Failure to follow
these instructions may cause an electrical
shock and/or sparks that could cause an explo-
sion in class 1, div. 2 hazardous locations.
Returning the Controller to its Case
1. Ensure that the orientation of the controller is
correct and slide it back into the housing.
2. Using your thumbs push on either side of the
controller until both latches click.
Note:
The controller is keyed so if it feels that it will
not slide back in do not force it. Check the ori-
entation again and reinsert after correcting.
Chemical Compatibility
This product is compatible with acids, weak
alkalis, alcohols, gamma radiation and ultra-
violet radiation.
This product is not compatible with strong
alkalis, organic solvents, fuels, aromatic
hydrocarbons, chlorinated hydrocarbons,
esters and keytones.
Terminal Definitions
Slot C Terminal Function Model
98
99
power input: ac or dc+
power input: ac or dc-
PM _(C)_ _ _ - AAAAB _ _
CF
CD
CE
Standard Bus EIA-485 common
Standard Bus EIA-485 T-/R-
Standard Bus EIA-485 T+/R+
PM _(C)_ _ _ - AAAAB _ _
Slot A
Input 1
T1
S1
R1
S2 (RTD) or current +,
S3 (RTD), thermocouple -, current - or
volts -
S1 (RTD), thermocouple + or volts +
Universal Sensor
input 1: all configurations
Outputs Terminal Function Configuration
12
X1
W1
Y1
common (Any switched dc output can
use.)
dc- (open collector)
dc+
Switched dc/open collector, output 1:
PM _(C)_ C _-_ AAAB _ _
W2
Y2
dc-
dc+
Switched dc, output 2:
PM _ (C) _ _ C - _ AAAB _ _
F1
G1
H1
voltage or current -
voltage +
current +
Universal Process, output 1:
PM _ (C) _ F _ - _ AAAB _ _
L1
K1
J1
normally open
common
normally closed
Mechanical Relay 5 A, Form C, output 1:
PM _(C)_ E _-_ AAAB _ _
L2
K2
normally open
common
NO-ARC 15 A, Form A, output 2:
PM6(C) _ _ H - _ AAAB _ _
L2
K2
normally open
common
Mechanical Relay 5 A, Form A, output 2:
PM _(C)_ _ J-_ AAAB _ _
L1
K1
L2
K2
normally open
common
Solid-State Relay 0.5 A, Form A
output 1: PM _(C)_ K _ - _ AAAB _ _
output 2: PM _(C)_ _ K - _ AAAB _ _
Dimensions 1/16 DIN
15.8 mm
(0.62 in)
101.6 mm
(4.00 in)
53.3 mm
(2.10 in)
53.3 mm
(2.10 in)
51.2 mm
(2.02 in)
Side
Front
Top
21.6 mm
(0.85 in)
45.2 mm
(1.78 in)
45.2 mm
(1.78 in)
21.6 mm
(0.85 in)
Recommended panel spacing
panel thickness 1.53 to 9.52 mm
(0.060 to 0.375)
5
6
7
8
Note:
In the pictures below notice that the Slot A connector does not show labeling for the outputs. Labeling
for Slot A outputs is based on the controller part number.
S
lot A
Slot B
Slot C
Output 1 Output 2
98
99
CF
CD
CE
T1
S1
R1
98 99
CF CD CE
Slot C
Slot A
Output 1 Output 2
C
A
T1 S1 R1
Power
Power
power
power
98
99
CF
CD
CE
Slot C
fuse
• 47 to 63 Hz
• 10VA maximum power consumption
Low Power
• 12 to 40VÎ (dc)
• 20 to 28VÅ (ac) Semi Sig F47
High Power
85 to 264VÅ (ac)
•100 to 240VÅ (ac) Semi Sig F47
Ó
Warning:
Use National Electric (NEC) or other country-
specific standard wiring and safety practices
when wiring and connecting this controller to
a power source and to electrical sensors or
peripheral devices. Failure to do so may result in
damage to equipment and property, and/or injury
or loss of life.
Note:
Maximum wire size termination and torque rating:
0.0507 to 3.30 mm
2
(30 to 12 AWG) single-
wire termination or two 1.31 mm
2
(16 AWG)
• 0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled differently,
depending on the model number.
Note:
To prevent damage to the controller, do not con-
nect wires to unused terminals.
Note:
Maintain electrical isolation between analog input