User`s manual
Watlow EZ-ZONE™ RUI/Gateway • 15 • Chapter 5 Networking with a Gateway
HMI, PC, PLC
RUI/Gateway (gtW) Setup Prompts
gtW = 1 – 16
(Gateway Instance)
Du;En = Yes or No
(Enable gateway instance)
Gateway
Du;st = On or off
(Device Status)
MoF = 0 - 9999
(Modbus Offset)
Modbus
Com Instance 1
Standard Bus Address
Ad;S = 1-8
Start Node to Scan
St;2n = 1-16
End Zone to Scan
nU;2n = 1-16
gtW 1 = PM1
gtW 4 = PM4
Watlow Standard Bus
(Daisy chain EIA-485)
EZ-ZONE Controllers
1 - 16 maximum
Modbus Offset
0
Modbus Offset
15000
Modbus Offset
10000
Modbus Offset
5000
Baud Rate
baud = 9.6, 19.2, 38.4kb
Com Instance 2
Modbus Address
Ad;m = 1-247
Parity
par = none, euen, odd
Modbus Word Order
M;hl = lohi or hilo
Note: To minimize traffic and enable better throughput on Stan-
dard Bus, set the End Zone prompt in the RUI to the maximum
number of EZ-ZONE controllers on the network to be scanned.