User`s guide

Series D8 User’s Guide Chapter 2: Installation
Doc. 0600-3120-2000 Watlow Anafaze 37
TB50 Connections
Table 2.7 TB50 Connections
1
The indicated outputs are dedicated for control when enabled in the
loop setup. If one or both of a loop’s outputs are disabled, the corre-
sponding digital outputs become available for alarms or programmable
logic.
2
If you install a Watlow Anafaze Serial DAC, the D8 uses digital output
18 (terminal 42) for a clock line. You cannot use output 18 for anything
else if a Serial DAC is installed.
Control Output
1
Control Output
1
Ter-
minal
Function D88 D84
Ter-
minal
Function D88 D84
1 +5 Vdc 2 +5 Vdc
3 CTRL COM 4 CTRL COM
5 Not used 6 Watchdog
Timer
7 Not used 8 Global Alarm
9 Output 1 Loop 1 heat Loop 1 heat 10
Not used
11 Output 2 Loop 2 heat Loop 2 heat 12 Not used
13 Output 3 Loop 3 heat Loop 3 heat 14 Not used
15 Output 4 Loop 4 heat Loop 4 heat 16 Not used
17 Output 5 Loop 5 heat Loop 1 cool 18 Not used
19 Output 6 Loop 6 heat Loop 2 cool 20 Not used
21 Output 7 Loop 7 heat Loop 3 cool 22 Not used
23 Output 8 Loop 8 heat Loop 4 cool 24 Not used
25 Output 9 Loop 1 cool 26 Not used
27 Output 10 Loop 2 cool 28 Not used
29 Output 11 Loop 3 cool 30 Not used
31 Output 12 Loop 4 cool 32 Not used
33 Output 13 Loop 5 cool 34 Not used
35 Output 14 Loop 6 cool 36 Not used
37 Output 15 Loop 7 cool 38 Not used
39 Output 16 Loop 8 cool 40 Not used
41 Output 17 42
Output 18
2
Serial
DAC clock
43 Input 1 44 Input 2
45 Input 3 46 Input 4
47 Input 5 48 Input 6
49 Input 7 50 Input 8