User`s guide

Chapter 7: Troubleshooting and Reconfiguring Series D8 User’s Guide
174 Watlow Anafaze Doc. 0600-3120-2000
Voltage Inputs
For each voltage input, you must install two resistors. The re-
sistances must be correct for the expected input range. Note
the resistor pack (RP) locations have three through-holes. In-
stall the RD resistor as indicated in the illustration below.
Table 7.7 Resistor Values for Voltage Inputs
Resistor tolerance: ±0.1%
Table 7.8 Resistor Locations for Voltage In-
puts
Input Range
Resistor Values
RC RD
0 to 100 mVdc 499 750
0 to 500 mVdc 5.49 k 750
0 to 1 Vdc 6.91 k 442.0
0 to 5 Vdc 39.2 k 475.0
0 to 10 Vdc 49.9 k 301.0
0 to 12 Vdc 84.5 k 422.0
Loop
Resistor Locations
RC RD
1 R58 RP1
2 R56 RP2
3 R54 RP3
4 R52 RP4
5 R50 RP5
6 R48 RP6
7 R46 RP7
8 R44 RP8
RP#
RD