User`s guide
Chapter 6: Menu and Parameter Reference Series D8 User’s Guide
144 Watlow Anafaze Doc. 0600-3120-2000
Values: For a thermocouple or RTD input, any value within
the input range (see Table 6.7 ). For a process or pulse input,
any value between the Input range low and Input range high
parameters.
Default: 760. Decimal placement depends upon the Input
type and Disp format settings.
Decimal Placement for DeviceNet: See Decimal Placement
for Numeric Values on page 59.
DeviceNet Object: Alarm (67 hex)
Alarm High Function
Choose whether the high alarm functions as an alarm or as a
boost output, or disable the alarm.
Values: See Table 6.14 on page 144.
Default: off
DeviceNet Object: See Alarm Acknowledge on page 153 and
Alarm Function on page 154.
Table 6.14 Alarm Functions
Alarm High Output
Choose a digital output to activate when the high alarm oc-
curs. You cannot choose an output that is in use for closed-
loop control or for the Serial DAC clock.
Values: none (0) or output 1 to 18 (1 to 18). Values in paren-
theses are for communications.
Default: none (0)
DeviceNet Object: Alarm (67 hex)
Value Description
off
No alarm function.
standard
Alarm is indicated and logged.
Latching global alarm is activated.
Alarm must be acknowledged to clear.
Optional non-latching alarm output is acti-
vated.
boost
Alarm message on controller display only.
Alarm does not require acknowledgement.
Non-latching alarm output is activated. Use
the alarm set points to control this output for
boost control.
l01 Alarm high r
func boff
l01 Alarm high r
outputbnone