User`s guide

Chapter 6: Menu and Parameter Reference Series D8 User’s Guide
142 Watlow Anafaze Doc. 0600-3120-2000
Sensor Fail Heat/Cool Output
A loop will switch to manual mode at the specified output
power if one of the following conditions occurs while in auto-
matic mode:
A failed sensor alarm occurs, or
The mode override input becomes active (see Mode
Override on page 127).
DeviceNet connection becomes inactive unexpectedly.
For most applications, this parameter should be set to 0% for
both heat and cool outputs.
Values: 0 to 100% (0 to 1000). Values in parentheses are for
communications.
Default: 0% (0)
Decimal Placement for DeviceNet: See Decimal Placement
for Percentage Values on page 60.
DeviceNet Object: Output (65 hex)
WARNING! Do not rely solely on the failed sensor alarm
to adjust the output in the event of a sensor
failure. If the loop is in manual mode when a
failed sensor alarm occurs, the output is not
adjusted. Install independent external safety
devices to shut down the system if a failure
occurs.
Open Thermocouple Heat/Cool Output Average
If you set this parameter to on and a thermocouple open alarm
occurs, a loop set to automatic control mode will switch to
manual mode at the average output prior to the alarm.
Values: on (1) or off (0). Values in parentheses are for com-
munications.
DeviceNet Object: Output (65 hex)
l01 Sensor failr
heat outputb 0%
l01 Open T/C htr
out average boff