Heat/Cool Integral
Enter the integral constant. A larger value yields less integral
action.
Values: 0 (off) to 6000 seconds per repeat
Default: For the Heat integral parameter, 180. For the Cool
integral parameter, 60.
DeviceNet Object: Control (66 hex)
Heat/Cool Derivative
Enter the derivative constant. A larger value yields greater de-
rivative action.
Values: 0 to 255 seconds
Default: 0
DeviceNet Object: Control (66 hex)
Heat/Cool Manual Reset
A process that uses only proportional control settles at a point
above or below the set point; it never reaches the set point.
This is known as offset or droop. At this parameter, enter the
power level required to maintain set point to compensate for
this offset.
Values: 0 to 100% (0 to 1000). Values in parentheses are for
communications.
Default: 0% (0)
Decimal Placement for DeviceNet: See Decimal Placement
for Percentage Values on page 60.
DeviceNet Object: Control (66 hex)
Heat/Cool Filter
Use this parameter to dampen the response of the heat or cool
output. The output responds to a change by going to approxi-
mately two-thirds of its final value within the specified num-
ber of scans. A larger value results in a slower response to
changes in the process variable.
Values: 0 (off) to 255
Default: 3
DeviceNet Object: Control (66 hex)
l01 Heat inte- r
gral b 180 sec/R
l01 Heat de- r
rivativeb 0 sec
l01 Heat manualr
reset b 0%
l01 Heat filterr
b 3 scans