User`s guide

Series D8 User’s Guide Chapter 6: Menu and Parameter Reference
Doc. 0600-3120-2000 Watlow Anafaze 131
Model and Firmware Version
The last parameter in the Global setup menu shows the con-
troller model (WATLOW D84 or WATLOW D88), the firm-
ware version (Vxx.xx), and the flash-memory checksum
(CS=xxxx).
DeviceNet Objects: Model: Identity (01 hex), Firmware Ver-
sion: N/A, Checksum: N/A.
Input Menu
Use the Input menu to configure the process input:
Input type
Engineering units
Scaling, calibration and filtering.
Input Type
Choose the type of sensor that is connected to the analog input.
Values: See Table 6.7.
Default: J thermocouple (1)
DeviceNet Object: Input (64 hex)
Table 6.7 Input Types and Ranges
Display
Value
DeviceNet
Value
Description Input Range
J t/c
1 Type J thermocouple -350 to 1400°F (-212 to 760°C)
K t/c
2 Type K thermocouple -450 to 2500° F (-268 to 1371°C)
T t/c
3 Type T thermocouple -450 to 750°F (-268 to 399°C)
S v
4 Type S thermocouple 0 to 3200°F (-18 to 1760°C)
R t/c
5 Type R thermocouple 0 to 3210°F (-18 to 1766°C)
B t/c
6 Type B thermocouple 150 to 3200°F (66 to 1760°C)
E t/c
20 Type E thermocouple -328 to 1448°F (-200 to 787°C)
RTD
8 RTD
-328.0 to 1150.0°F (-200.0 to 621.1°C)
process
0
Voltage or current signal,
depending upon the hardware
configuration. See Figure 1.2 on
page 6.
User defined. See Setting Up Pro-
cess Variable Retransmit on page
97.
skip
10
Loop is not used for control, does
not report alarms, and is not
shown on the scanning display.
(none)
lWATLOW D84 r
V1.00 cs=1234
l01 Input r
Other menus b
l01 Input type r
bJ T/C