User`s guide

Chapter 6: Menu and Parameter Reference Series D8 User’s Guide
128 Watlow Anafaze Doc. 0600-3120-2000
Mode Override Digital Input Active
Choose whether the on state (connected to controller com-
mon) or off state (open circuit) activates the mode override
feature.
Use the Mode override parameter to enable the mode override
feature and select the digital input.
Values: on (0) or off (1). Values in parentheses are for com-
munications.
Default: on (0)
DeviceNet Object: Global (6B hex)
Power Up Alarm Delay
Specify how long to delay high, low and deviation alarms on
all loops during powerup. This feature does not delay failed
sensor alarms.
Values: 0 to 60 minutes
Default: 0
DeviceNet Object: Global (6B hex)
Power Up Loop Mode
Choose the power-up state of the control outputs.
Values: See Table 6.5 on page 128.
Default: off (0)
DeviceNet Object: Global (6B hex)
WARNING! Do not set the controller to start from memo-
ry if it might be unsafe for the control outputs
to be on upon power up.
Table 6.5 Power Up Loop Modes
Display
Value
DeviceNet
Value
Description
off
0
Upon powerup, all loops are set to manual mode at 0 per-
cent output.
from memory
1
Upon powerup, all loops are restored to the previous control
mode and output power level.
lMode override r
D/I active bon
lPower up alarmr
delay b 0 min
lPower up loop r
modebmanual 0%