User`s guide

Series D8 User’s Guide Chapter 6: Menu and Parameter Reference
Doc. 0600-3120-2000 Watlow Anafaze 127
Values: 1=true (0) or 0=true (1). Values in parentheses are
for communications.
Default: 1=true (0)
DeviceNet Object: Global (6B hex)
Table 6.4 Digital Input States Required to
Load Each Job
Mode Override
Choose the digital input to use for the mode override feature.
When the input is activated, the controller sets all loops to
manual mode at the output levels specified at the Sensor fail
heat output and Sensor fail cool output parameters in the Out-
put menu.
Use the Mode override D/I active parameter to choose which
signal state activates the mode override feature.
Values: enabled by D/I1 to enabled by D/I8 (1 to 8) or dis-
abled (0). Values in parentheses are for communications.
Default: disabled (0)
DeviceNet Object: Global (6B hex)
WARNING! Do not rely solely on the mode override
feature to shut down your process. Install ex-
ternal safety devices or overtemperature de-
vices for emergency shutdowns.
Job
Digital Input
1 2 3
1FFF
2TFF
3FTF
4TTF
5FFT
6TFT
7FTT
8TTT
lMode override r
bdisabled