Series D8 User’s Guide Chapter 4: Operation and Setup
Doc. 0600-3120-2000 Watlow Anafaze 95
The RTD alarms are enabled on any channel with Input Type
set to RTD.
Restore Automatic Control After a Sensor Failure
This feature returns a loop to automatic control after a failed
sensor is repaired. To enable this feature:
Choose a digital input for the RestoreAuto parameter in
the Control menu.
Connect the digital input to the dc common terminal on
the controller.
Process Alarms
The D8 has four process alarms, each of which you can con-
figure separately for each loop:
Alarm low
Alarm high
Low deviation alarm
High deviation alarm
What Happens if a Process Alarm Occurs?
If a process alarm occurs, the controller does the following:
Shows an alarm code on the display. See Alarm Displays
on page 81.
Activates the global alarm output. See Global Alarm on
page 97.
Activates the digital output that is assigned to the process
alarm (if applicable). The digital output remains active
until the process variable returns within the correspond-
ing limit and hysteresis. The alarm output deactivates
when the process returns to normal.
Process Alarm Outputs
Any digital output that is not used as a control output can be
assigned to one or more process alarms.
The controller activates the output if any alarm assigned to the
output is active. Process alarm outputs are non-latching—that
is, the output is deactivated when the process returns to nor-
mal, whether or not the alarm has been acknowledged.
Specify the active state of process alarm outputs at the D/O
alarm polarity setting in the Global setup menu.