User`s manual

Watlow EZ-ZONE™ Communications 71 Chapter 2 Mobbus RTU & TCPWatlow EZ-ZONE™ Communications 71 Chapter 7 Setup Page
Parameter name
Description
Modbus
(less
40,001 off-
set)
read/write
CIP
class
instance
attribute
Range Default Data
Type
EZ-ZONE™
PM Int.*
EZ-ZONE™
PM PID*
EZ-ZONE™
PM Limt*
Digital Output 6
Function
Select what function will drive this output.
1038 r/w 106
6
5 r/w
Off (62)
Cool (20)
Heat (36)
Alarm (6)
Event (29)
Off integer X X X
Digital Output 6
Function Instance
Select which source instance will drive the
output.
1040 r/w 106
6
6 r/w
1 to 4 1 (output
5)
2 (output
6)
integer X X X
Digital Input 6
Level
Select what action will be interpreted as a
true state.
1340 r/w 110
2
1 r/w
High (37)
Low (53)
High integer X X X
Digital Input 6
Function
Select the function that will be triggered by
a true state.
1344 r/w 110
2
3 r/w
None (61)
Idle Set Point Enable (107)
Tune (98)
Alarm Reset (6)
Silence Alarms (108)
Manual/Auto Mode (54)
Control Outputs Off (90)
Remote Set Point Enable
(216)
Lock Keypad (217)
Force Alarm (218)
TRU-TUNE+™ Disable (219)
Alarm Outputs & Control
Loop Off (220)
Limit Reset (82)
Profile Disable (206)
Profile Hold/Resume (207)
Profile Start Number (196)
Profile Start/Stop (208)
Restore User Settings (227)
None integer X X X
Digital Input 6
Function Instance
Select which instance of the Event Function
will be triggered by a true state.
1342 r/w 110
2
2 r/w
0 All Instances (except pro-
files)
(For example, if Digital Func-
tion is set to Silence Alarms
and Function Instance is
set to 0, then this digital
input will silence both
alarms.)
1 to 4
1 integer X X X
Limit Menu
Limit
Sides
Select which side or sides of the process
value will be monitored.
688 r/w 112
1
5 r/w
Both (13)
High (37)
Low (53)
Both integer X X
Integers are unsigned, 16-bit values. Floating point values are IEEE 754 32-bit floating point values.
The default Modbus order is Low Word-High Word. The order can be changed in the Communications Menu.
The default serial data format is: 9,600 baud; 8 data bits; no parity; 1 stop bit.
NOTE: Avoid continuous writes within loops. Excessive writes to the EEPROM will cause premature EEPROM failure. The EEPROM is
rated for 1,000,000 writes.
Underlined parameters are not accessable using a remote user's interface (RUI) or the controller's front panel. They can only be ac-
cessed using communications.
*Some of the parameters are not functional in some configurations of each model. Check the user's manual for information.
Int.
PID
Lmt.