User`s manual
Watlow EZ-ZONE™ Communications • 69 • Chapter 2 Mobbus RTU & TCPWatlow EZ-ZONE™ Communications • 69 • Chapter 7 Setup Page
Parameter name
Description
Modbus
(less
40,001 off-
set)
read/write
CIP
class
instance
attribute
Range Default Data
Type
EZ-ZONE™
PM Int.*
EZ-ZONE™
PM PID*
EZ-ZONE™
PM Limt*
Analog Input 2
RTD Leads
Set to match the number of leads on the
RTD wired to this input.
452 r/w 104
2
7 r/w
2
3
2 floating
point
X
Analog Input 2
Scale Low
Set the low scale for process inputs. This
value, in millivolts, volts or milliamps, will
correspond to the Range Low displayed by
the controller.
468 r/w 104
2
16 r/w
-100.0 to 1,000.0 0.0 floating
point
X
Analog Input 2
Scale High
Set the high scale for process inputs. This
value, in millivolts, volts or milliamps, will
correspond to the Range High displayed by
the controller.
470 r/w 104
2
16 r/w
-100.0 to 1,000.0 20.0 floating
point
X
Analog Input 2
Range Low
Set the low range for the displayed process
input units.
472 r/w 104
2
15 r/w
-1,999.000 to 9,999.000 0.0 floating
point
X
Analog Input 2
Range High
Set the high range for the displayed process
input units.
474 r/w 104
2
18 r/w
-1,999.000 to 9,999.000 9,999.0 floating
point
X
Analog Input 2
Process Error Enable
Turn the Process Error Low feature on or off.
498 r/w 104
2
30 r/w
Off (62)
Low
Off integer X
Analog Input 2
Process Error Low
If the process value drops below this value, it
will trigger an input error.
500 r/w 104
2
31 r/w
-100.0 to 1,000.0 0.0 floating
point
X
Analog Input 2
Filter Time
Filtering smooths out the process signal to
both the display and the input. Increase the
time to increase filtering.
466 r/w 104
2
14 r/w
0.0 to 60.0 seconds 0.5 floating
point
X
Analog Input 2
Error Latching
Turn input error latching on or off. If latch-
ing is on errors must be manually cleared.
494 r/w 104
2
28 r/w
Off (62)
On (63)
Off integer X
Analog Input 2
Decimal
Set the precision of the displayed value.
478 r/w 104
2
20 r/w
Whole (105)
Tenths (94)
Hundredths (40)
Thousandths (96)
Whole integer X
Input 2
Error Reset
Write to this register to clear an error state.
496 w 104
2
29 w
0 integer X
Digital Input/Output Menu
Digital Input or Ouput 5 Submenu
Integers are unsigned, 16-bit values. Floating point values are IEEE 754 32-bit floating point values.
The default Modbus order is Low Word-High Word. The order can be changed in the Communications Menu.
The default serial data format is: 9,600 baud; 8 data bits; no parity; 1 stop bit.
NOTE: Avoid continuous writes within loops. Excessive writes to the EEPROM will cause premature EEPROM failure. The EEPROM is
rated for 1,000,000 writes.
Underlined parameters are not accessable using a remote user's interface (RUI) or the controller's front panel. They can only be ac-
cessed using communications.
*Some of the parameters are not functional in some configurations of each model. Check the user's manual for information.
Int.
PID
Lmt.