User`s manual

Watlow EZ-ZONE™ Communications 68 Chapter 2 Mobbus RTU & TCPWatlow EZ-ZONE™ Communications 68 Chapter 7 Setup Page
Parameter name
Description
Modbus
(less
40,001 off-
set)
read/write
CIP
class
instance
attribute
Range Default Data
Type
EZ-ZONE™
PM Int.*
EZ-ZONE™
PM PID*
EZ-ZONE™
PM Limt*
Analog Input 1
Range High
Set the high range for the displayed process
input units.
394 r/w 104
1
18 r/w
-1,999.000 to 9,999.000 9,999.0 floating
point
XXX
Analog Input 1
Process Error Enable
Turn the Process Error Low feature on or off.
418 r/w 104
1
30 r/w
Off (62)
Low (53)
Off integer X X X
Analog Input 1
Process Error Low
If the process value drops below this value, it
will trigger an input error.
420 r/w 104
1
31 r/w
-100.0 to 1,000.0 0.0 floating
point
XXX
Analog Input 1
Filter Time
Filtering smooths out the process signal to
both the display and the input. Increase the
time to increase filtering.
386 r/w 104
1
14 r/w
0.0 to 60.0 seconds 0.5 floating
point
XXX
Analog Input 1
Error Latching
Turn input error latching on or off. If latch-
ing is on errors must be manually cleared.
414 r/w 104
1
28 r/w
Off (62)
On (63)
Off integer X X X
Analog Input 1
Decimal
Set the precision of the displayed value.
398 r/w 104
1
20 r/w
Whole (105)
Tenths (94)
Hundredths (40)
Thousandths (96)
Whole integer X X X
Analog Input 1
Sensor Backup Enable
If the input 1 sensor fails, the controller will
use the input 2 sensor.
410 r/w 104
1
26 r/w
Off (62)
On (63)
Off integer X
Analog Input 1
Error Reset
Write to this register to clear an error state.
416 w 104
1
29 w
0 integer X X X
Analog Input 2 Submenu
Analog Input 2
Sensor Type
Set the analog sensor type to match the de-
vice wired to this input.
Note: There is no open-sensor detection for pro-
cess inputs.
448 r/w 104
2
5 r/w
Off (62)
Thermocouple (95)
Millivolts (56)
Volts dc (104)
Milliamps dc (112)
RTD 100 Ω (113)
RTD 1,000 Ω (114)
Potentiometer 1 kΩ (155)
Thermo-
couple
integer X
Analog Input 2
Linearization
Set the linearization to match the thermo-
couple wired to this input.
450 r/w 104
2
6 r/w
B (11) K (48)
C (15) N (58)
D (23) R (80
E (26) S (84)
F (30) T (93)
J (46)
J
integer X
Integers are unsigned, 16-bit values. Floating point values are IEEE 754 32-bit floating point values.
The default Modbus order is Low Word-High Word. The order can be changed in the Communications Menu.
The default serial data format is: 9,600 baud; 8 data bits; no parity; 1 stop bit.
NOTE: Avoid continuous writes within loops. Excessive writes to the EEPROM will cause premature EEPROM failure. The EEPROM is
rated for 1,000,000 writes.
Underlined parameters are not accessable using a remote user's interface (RUI) or the controller's front panel. They can only be ac-
cessed using communications.
*Some of the parameters are not functional in some configurations of each model. Check the user's manual for information.