User`s manual
Watlow EZ-ZONE™ Communications • 65 • Chapter 6 Operations Page
Parameter name
Description
Modbus
(less
40,001
offset)
read/
write
CIP
class
instance
attribute
read/
write
Range Default Data
Type
EZ-ZONE™
PM Int.*
EZ-ZONE™
PM PID*
EZ-ZONE™
PM Limt*
Current
Read
View the most recent value monitored by
the current transformer.
1120 r N.A. -1,999.000 to 9,999.000 floating
point
X
Current
Error
View the cause of the most recent load
fault.
1122 r N.A.
None (61)
Shorted (127)
Open (65)
None integer
X
Current
Heater Error
View the cause of the most recent load fault
monitored by the current transformer.
1124 r N.A.
None (61)
High (37)
Low (53)
None integer
X
Current
Detect Threshold
For factory use.
1142
r/w
N.A. 3 to 59 9 integer
X
Current
Error Status
View the cause of the most recent load fault
monitored by the current transformer.
1160 r N.A.
None (61)
Fail (32)
None integer
X
Current
Scaling
Scale the current reading to match the cur-
rent transformer.
1162
r/w
N.A. 0 to 9,999.000 50 floating
point
X
Current
Reading Enable
Set to Yes to enable the controller to display
the current error message.
1126 r N.A. Yes (59)
No (106)
No integer
X
Profile Status Menu
* Some parameters in the Profile Status Menu can be changed for the currently
running profile, but should only be changed by knowledgeable personnel and
with caution. Changing parameters via the Profile Status Menu will not change
the stored profile but will have an immediate impact on the profile that is run-
ning.
Changes made to profile parameters in the Profiling Pages will be saved and
will also have an immediate impact on the running profile.
Profile Status
Start
Select a profile or step that will be affected
by Profile Action Request.
2520
r/w
122
1
1 r/w
0 to 40 0 (none)
integer X X
Profile Status
Action Request
Select the action to apply to the profile (1 to
4) or step selected in Start.
2540 r 122
1
11 r/w
None (61)
Start a Profile (196)
Start a Step (89)
Pause (146)
Resume (147)
End (148)
None
integer X X
Profile Status
Active Profile
View the currently loaded profile.
2524 r 122
1
3 r
1 to 4 0 (none)
integer X X
Profile Status
Active Step
View the currently running step.
2528 r 122
1
4 r
0 to 40 0 (none)
integer X X
Integers are unsigned, 16-bit values. Floating point values are IEEE 754 32-bit floating point values.
The default Modbus order is Low Word-High Word. The order can be changed in the Communications Menu.
The default serial data format is: 9,600 baud; 8 data bits; no parity; 1 stop bit.
NOTE: Avoid continuous writes within loops. Excessive writes to the EEPROM will cause premature EEPROM failure. The EEPROM is
rated for 1,000,000 writes.
Underlined parameters are not accessable using a remote user's interface (RUI) or the controller's front panel. They can only be ac-
cessed using communications.
*Some of the parameters are not functional in some configurations of each model. Check the user's manual for information.
Int.
PID
Lmt.