User`s manual

Watlow EZ-ZONE™ Communications 34 Chapter 3 EtherNet/IP
Originator to Target (O to T) - Default Assembly
Table 3.7
Attribute Name EIP Class ID EIP Instance
ID
EIP Attribute
ID
Data Type
Loop Control Mode 151 1 1 DINT
Closed Loop Set Point 107 1 1 REAL
Open Loop Set Point 107 1 2 REAL
Alarm 1 High Set Point 109 1 1 REAL
Alarm 1 Low Set Point 109 1 2 REAL
Alarm 2 High Set Point 109 2 1 REAL
Alarm 2 Low Set Point 109 2 2 REAL
Alarm 3 High Set Point 109 3 1 REAL
Alarm 3 Low Set Point 109 3 2 REAL
Alarm 4 High Set Point 109 4 1 REAL
Alarm 4 Low Set Point 109 4 2 REAL
Profile Action Request 122 1 11 DINT
Profile Start 122 1 1 DINT
Heat Proportional Band 151 1 6 REAL
Cool Proportional Band 151 1 7 REAL
Time Integral 151 1 8 REAL
Time Derivative 151 1 9 REAL
Heat Hysteresis 151 1 11 REAL
Cool Hysteresis 151 1 12 REAL
Deadband 151 1 10 REAL
In using the output assembly define the following sizes based on the configured “Comm Format” in
RSLogix5000.
DINT: 20
INT: 40
Note: Excessive writes to the PM may cause premature EEPROM failure. If using the O to T assembly it is recommended that EE-
PROM writes be disabled (factory default).
For more detail see the section entitled "Saving Settings to Nonvolatile Memory".