User`s manual
Watlow EZ-ZONE™ Communications • 30 • Chapter 3 EtherNet/IP
EtherNet/IP Indicator Lights
The PM has four indicator lights on the top of the controller, all of which are used with EtherNet/IP. The
characteristics of the Module Status and Network Status LED’s are defined by Open DeviceNet Vendors As-
sociation (ODVA), while the Active and Link indicator lights are defined in the Ethernet specification.
Module Status Indicator
Table 3.1
Indicator State Summary Requirement
Steady Off No power
If no power is supplied to the device, the module status indicator
shall be steady off.
Steady Green
Device
operational
If the device is operating correctly, the module status indicator
shall be steady green.
Flashing Green Standby
If the device has not been configured, the module status indicator
shall be flashing green.
Flashing Red Minor fault
If the device has detected a recoverable minor fault, the module
status indicator shall be flashing red.
NOTE: An incorrect or inconsistent configuration would be con-
sidered a minor fault.
Steady Red Major fault
If the device has detected a non-recoverable major fault, the mod-
ule status indicator shall be steady red.
Flashing Green /
Red
Self-test
While the device is performing its power up testing, the module
status indicator shall be flashing green / red.
Steady Off
Not powered,
no IP address
If the device does not have an IP address (or is powered off), the
network status indicator shall be steady off.
Flashing Green No connections
If the device has no established connections, but has obtained an
IP address, the network status indicator shall be flashing green.
Steady Green Connected
If the device has at least one established connection (even to the
Message Router), the network status indicator shall be steady
green.
Flashing Red
Connection
timeout
If one or more of the connections in which this device is the target
has timed out, the network status indicator shall be flashing red.
This shall be left only if all timed out connections are reestab-
lished or if the device is reset.
Steady Red Duplicate IP
If the device has detected that its IP address is already in use,
the network status indicator shall be steady red.
Flashing Green /Red Self-test
While the device is performing its power up testing, the network
status indicator shall be flashing green / red.
Table 3.2
Network Status Indicator
Steady Off
Not powered,
unknown link speed
If the device cannot determine link speed or power is off,
the network status indicator shall be steady off.
Red Link speed = 10 Mbit
If the device is communicating at 10 Mbit, the link LED
will be red..
Green Link speed = 100 Mbit
If the device is communicating at 100 Mbit, the link LED
will be green.
Table 3.3
Link Status Indicator
Flashing Green Detects activity If the MAC detects activity, the LED will be flashing green.
Red Link speed = 10Mbit If the MAC detects a collision, the LED will be red.
Table 3.4
Activity Status Indicator