Watlow EZ-ZONE™ Communications • 14 • Chapter 2 Mobbus RTU & TCP
Binary Hex Decimal Purpose
00000001 01 1 Controller Address
00010000 10 16 Function Multiple Write
00000000 08 8 High Byte of Register 2160 decimal – Start writing at register
01110000 70 112 Low Byte of Register 2160 decimal – Start writing at register
00000000 00 0 High Byte – number of registers written
00000010 02 2 Low Byte – number of registers written
01000010 42 66 Low byte of CRC
01110011 73 115 High byte of CRC
Received from Writing Closed Loop Set Point of 75.0
o
F
Table 2.4