Watlow EZ-ZONE™ Communications • 118 • Chapter 8 Profiling Page
Parameter name
Description
Modbus
(less
40,001
offset)
read/write
CIP
class
instance
attribute
Range Default Data
Type
EZ-ZONE™
PM Int.*
EZ-ZONE™
PM PID*
Step 27 Parameters
Wait For Process Instance
Select which analog input Wait For Process will use.
3898
r/w
121
27
15 r/w
1 or 2 1 integer
X
Step 27 Parameters
End Type
Select what the controller will do when this profile ends.
3896
r/w
121
27
14 r/w
Control Mode set to Off
(62)
Hold last closed-loop set
point in the profile (47)
User, reverts to previous
set point (100)
User integer
XX
Step 28 Menu
Step 28 Parameters
Step 28 Type
Select a step type.
3920
r/w
121
28
1 r/w
Unused Step (50)
Time (143)
Rate (1120)
Soak (87)
Wait For Event (144)
Wait For Process (209)
Wait For Both (210)
Jump Loop (116)
End (27)
Unused
integer X X
Step 28 Parameters
Target Set Point
Select the set point for this step.
3922
r/w
121
28
2 r/w
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
floating
point
XX
Step 28 Parameters
Hours
Select the hours (plus Minutes and Seconds) for a timed step.
3924
r/w
121
28
3 r/w
0 to 99 0 integer
XX
Step 28 Parameters
Minutes
Select the minutes (plus Hours and Seconds) for a timed step.
3926
r/w
121
28
4 r/w
0 to 59 0 integer
XX
Step 28 Parameters
Seconds
Select the seconds (plus Hours and Minutes) for a timed step.
3928
r/w
121
28
5 r/w
0 to 59 0 integer
XX
Step 28 Parameters
Rate
Select the rate for ramping in degrees or units per minute.
3930
r/w
121
28
6 r/w
0 to 9,999.000°F or units
per minute
0 to 5,555.000°C
0.0 floating
point
XX
Step 28 Parameters
Event Output 1
Select whether Event Output 1 is on or off during this step.
3932
r/w
121
28
7 r/w
Off (62)
On (63)
Off integer
XX
Step 28 Parameters
Event Output 2
Select whether Event Output 2 is on or off during this step.
3934
r/w
121
28
8 r/w
Off (62)
On (63)
Off integer
XX
Step 28 Parameters
Wait Event 1
Select the event state that must be satisfied during this step.
Digital input 5 provides the state of this event.
3936
r/w
121
28
9 r/w
Off (62)
On (63)
None (61)
Off integer
XX
Step 28 Parameters
Wait Event 2
Select the event state that must be satisfied during this step.
Digital input 6 provides the state of this event.
3938
r/w
121
28
10 r/w
Off (62)
On (63)
None (61)
Off integer
XX
Step 28 Parameters
Wait For Process Instance
Select which analog input Wait For Process will use.
3948
r/w
121
28
15 r/w
1 or 2 1 integer
X
Integers are unsigned, 16-bit values. Floating point values are IEEE 754 32-bit floating point values.
The default Modbus order is Low Word-High Word. The order can be changed in the Communications Menu.
The default serial data format is: 9,600 baud; 8 data bits; no parity; 1 stop bit.
NOTE: Avoid continuous writes within loops. Excessive writes to the EEPROM will cause premature EEPROM failure. The EEPROM is rated for
1,000,000 writes.
*Some of the parameters are not functional in some configurations of each model. Check the user's manual for information.